background image

7

6

4

5

2

1

5

3

1 2 3 4 5 6 7 8 9 10 11 12

17

16-MENU ITEMS AND OPERATION

Technical Dept. - All rights reserved - Reproduction prohibited

SYSTEM WITH: PELLET STOVE AND PUFFER

Adjustable setting

SET

VALUES

PUFFER TEMP.

55°C - 75°C

Parameters to be set

Settings

Value

Configuration

5

Hydraulic diagram

Num.

Description

Num.

Description

1

Pellet Boiler

5

Puffer probe

2

Rear terminal block

6

System pump

3

Anti-condensation valve

7

Room thermostat

4

Puffer

Содержание LOTO HYDRO 16

Страница 1: ...INSTALLATION GUIDE GB Instructions in English PELLET STOVE LOTO HYDRO 16 LOTO HYDRO 23 LOTO HYDRO 23 with exchanger PART 2 OPERATION AND CLEANING...

Страница 2: ...TS II 14 PRECAUTIONS BEFORE START UP 3 15 CONTROL PANEL 4 16 MENU ITEMS AND OPERATION 5 17 SAFETY DEVICES AND ALARMS 21 18 RECOMMENDATIONS FOR SAFE USE 25 19 CLEANING AND MAINTENANCE 26 20 FAULTS CAUS...

Страница 3: ...Pellet stove accessories Itisgoodpracticetoensureeffectiveventilationintheroomduringtheinitialstart up astheboilerwillemitsome smokeandsmellofpaint ATTENTION Please ensure the brazier is clear of ALL...

Страница 4: ...ng functions 7 Display MAIN MENU Press key 3 menu to access The options accessed are Date andTime Timer Sleep only when boiler is on Settings Info Date and time configuration Configure the time and da...

Страница 5: ...ctivate P1 press and select ON press the Menu key to confirm At this point the start time is 00 00 Press the key to set the start time and press the menu key to confirm Next the proposed stop time is...

Страница 6: ...ng the ON key turns on the boiler the boiler then stops automatically at the next time of the timer SLEEP FUNCTION main menu Sleep may be activated only when the boiler is on and allows you to quickly...

Страница 7: ...ng emissions in field o System configuration factory settings system 02 p Season q Technical menu NOTE Some of the options listed above cannot be enabled in certain system configurations a Language Se...

Страница 8: ...er it must be provided by the user The temperature of the boiler can also be controlled by an external thermostat in the room It should be positioned centrally in the room where the boiler is installe...

Страница 9: ...wntotheEcoStopareshownatthetopofthe display The flame moves to P1 and remains there until the set T Eco Stop time reaches zero and if the conditions are still satisfied turns off the boiler The ECO st...

Страница 10: ...scroll through and select Settings Press menu to confirm Scroll with the arrows and select Pellet recipe Press menu to confirm Alter the with the keys Press menu to confirm and esc to exit k Fumes rp...

Страница 11: ...h the panel displays the countdown 3 way valve the 3 way valve is activated for a fixed test period of 1 minute during which the panel displays the countdown in seconds Enable the Component test funct...

Страница 12: ...enables the auto eco function cannot be deactivated The room temperature probe external thermostat are ignored Modify the function as follows Press the menu key Use the arrow keys to scroll through a...

Страница 13: ...exchanger in FACTORY CONFIGURATION 2 2 Room temperature control via boiler s on board probe or enabling external thermostat DHW production for storage cylinder or storage with thermostat optional DIS...

Страница 14: ...ELLET STOVE AND ROOMTHERMOSTAT Adjustable setting SET VALUES WATERTEMP 30 C 80 C Parameters to be set Settings Value Configuration 1 External thermostat ON Hydraulic diagram Num Description Num Descri...

Страница 15: ...AND DHW STORAGE CYLINDER Adjustable setting SET VALUES AMBIENTTEMP 5 C 35 C WATERTEMP 30 C 80 C BOILERTEMP 30 C 80 C Parameters to be set Settings Value Configuration 3 Hydraulic diagram Num Descripti...

Страница 16: ...setting SET VALUES WATERTEMP 30 C 80 C BOILERTEMP 30 C 80 C Parameters to be set Settings Value Configuration 3 External thermostat ON Hydraulic diagram Num Description Num Description 1 Pellet Boile...

Страница 17: ...n prohibited SYSTEMWITH PELLET STOVE AND PUFFER Adjustable setting SET VALUES PUFFERTEMP 55 C 75 C Parameters to be set Settings Value Configuration 5 Hydraulic diagram Num Description Num Description...

Страница 18: ...FERTEMP 55 C 75 C Parameters to be set Settings Value Configuration 5 Auxiliary Boiler ON Hydraulic diagram Num Description Num Description 1 Pellet Boiler 7 Plate heat exchanger 2 Rear terminal block...

Страница 19: ...rnal thermostat by the temperature of the water in the boiler or by the NTC probes ELECTRICAL CONNECTIONS TERMINAL BLOCK CONTACTS POS 1 2 EXTERNALTHERMOSTAT PUFFERTHERMOSTAT POS 8 NEUTRALTHREE WAYVALV...

Страница 20: ...the flashing flame symbol When the flame stops blinking the boiler has reached the operating condition for supplying power The default target room temperature is set at 20 C To change this setting fol...

Страница 21: ...urn off OFF Stand by ELECTRICAL SAFETY Theboilerisprotectedagainstviolentchangesincurrentbyageneralfuselocatedinthecontrolpanelatthebackoftheboiler Otherfuses that protect the circuit boards are locat...

Страница 22: ...ssary measures and or precautions must be adopted when performing maintenance cleaning and repairs Donottamperwiththesafetydevices Donotremovethesafetydevices Connecttheproducttoanefficientsmokeexpuls...

Страница 23: ...heck whether the room fan is working correctly if there is one A04 Smoke overtemperature The set smoke threshold has been exceeded Reduce the load of pellets SETTINGS menu Pellet recipe A05 Pressure s...

Страница 24: ...emperature exceeds the threshold again the shutdown phase will be repeated at minimum speed until the temperature falls BLACKOUT with boiler ON In the event of a blackout the boiler does the following...

Страница 25: ...fundamental to guarantee that the product is installed in compliance with standards in force Furthermore it is of the utmost importance to respect the following simple rules Every time the brazier is...

Страница 26: ...move brazier B Use the vacuum nozzle to clean away any ash from the area under the brazier We recommend performing this operation every 2 3 days depending on what type of pellet is being used Open doo...

Страница 27: ...ws select Cleaning confirmwiththe Menu key activatethecleaning ON withthe keys Thisprocedurestartsthesmokeextractoronthemaximum setting to expel the soot that becomes dislodged when the exchanger is c...

Страница 28: ...Use a vacuum cleaner to remove all fallen material PERIODIC CLEANING PERFORMED BY A QUALIFIEDTECHNICIAN CLEANINGTHE SMOKE EXTRACTOR COMPARTMENT In the area behind ash pan D there is the smoke cap E w...

Страница 29: ...ng and maintenance as they will carryoutallofthepreviouslymentionedworkandinspectthestovecomponents SHUTDOWN end of season At the end of each season before switching the product off it is recommended...

Страница 30: ...eel panel depending on the type of stove Unscrew the screw washer rubber bushing roller shown in figure A C on both sides of the cover It is now possible to assemble the new kit Prepare the screw wash...

Страница 31: ...areessentialfor the correct operation of the product Gear motor Smoke extractor fan Smoke probe Ignition spark plug Pellet water automatic rearm thermostat Room water temperature probe Motherboard Fus...

Страница 32: ...tboard The fire goes out or the boiler stops automatically The pellet hopper is empty Fill the tank with pellets The pellets are not fed See the previous anomaly The pellet temperature safety probe ha...

Страница 33: ...does not work No electrical supply to the boiler Check the mains voltage and the protection fuse The motor is faulty Checkthemotorandcapacitorandreplace them ifnecessary Defective motherboard Replacet...

Страница 34: ...temperature Insufficient fuel consumption Checktherecipeand ortechnical parameters Radiators cold in winter Room thermostat local or remote set too low If remote thermostat check if it is defective Se...

Страница 35: ...BOILER CONNECTION TERMINAL 12 AUGER 13 SMOKE SENSOR 14 EXTERNALTHERMOSTAT CONNECTION TERMINAL 15 ROOMTEMPERATURE PROBE 16 PUFFER BOILER PROBE CONNECTION TERMINAL 17 BOILERWATERTEMPERATURE PROBE 18 SM...

Страница 36: ...REV 0 8901636300 Via La Croce n 8 33074Vigonovo di Fontanafredda PN ITALY Telephone 0434 599599 a s Fax 0434 599598 Internet www mcz it e mail mcz mcz it 27 06 2017...

Отзывы: