2-INSTALLATION

Technical Dept. - All rights reserved - Reproduction prohibited

CONNECTION TO THE FLUE

The connection between the flue and the appliance must be via a smoke duct that complies with EN 1856-2. The connecting section must 

extend no more than 4 m horizontally, with a minimum slope of 3% and with a maximum of 3 90% bends (accessible for inspection - do 

not count the Tee fitting at the appliance outlet).

The diameter of the smoke duct must be equal to or greater than that of the outlet of the appliance (Ø 100 mm). 

TYPE OF SYSTEM

SMOKE DUCT

Maximum length 

(with 1 accessible 90° bend)

6.5 metres

Maximum length 

(with 3 accessible 90° bends)

4.5 metres

Maximum number of accessible 90° bends

3

Horizontal sections

(minimum slope 3%)

4 metres

Use

 smoke ducts with a 

diameter 100 mm and silicone gaskets or similar gaskets that can withstand the high operating temperatures 

of the appliance (min. T200 class P1). 

The use of flexible metal hoses made of fibre cement or aluminium is forbidden. For 

direction changes, we always recommend the use of a Tee fitting

 with an inspection cap ensuring easy access to clean the pipes. 

Always ensure that the inspection cap is put back in place and sealed hermetically with the relevant seal intact after cleaning.

It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from hoods above it. It is forbidden to extract 

the combustion products directly through the wall, whether into indoor spaces or outdoors. 

The smoke duct must be at a minimum distance of 400 mm from flammable or heat-sensitive structures.

We recommend in particular to check the data tags of the flue for the safety distances that must be respected in presence 

of combustible materials and the type of insulating material to be used. These indications must be followed rigorously to 

avoid serious harm to personnel and surrounding infrastructure.

Содержание SELECTA 35Q S1

Страница 1: ...INSTALLATION GUIDE EN Instructions in English PELLET BOILER SELECTA 35Q S1 PART 1 REGULATIONS AND ASSEMBLY...

Страница 2: ...DUCTION 1 1 WARNINGS AND WARRANTY CONDITIONS 2 2 INSTALLATION 9 3 DRAWINGS AND TECHNICAL CHARACTERISTICS 19 4 UNPACKING 22 5 POSITIONING 24 6 INSTALLATION AND DISASSEMBLY 25 7 HYDRAULIC CONNECTION 32...

Страница 3: ...manual is strictly technical and the property of RED No part of this manual may be translated into other languages adapted or reproduced even in part in other mechanical or electronic forms photocopie...

Страница 4: ...uct and any electronic appliances connected to it are used correctly and accidents are prevented This appliance can be used by children aged 8 years and above and persons with reduced physical sensory...

Страница 5: ...rly before lighting again Shut the stove down in the event of a breakdown or bad running and contact the specialised technician immediately Pellets must not be fed manually into the burner this wrong...

Страница 6: ...t support the product in order to guarantee adequate insulation especially if the flooring is made of flammable materials In the event of a malfunction of the ignition system do not force it to light...

Страница 7: ...EN 303 5 boilers In the case of tests for any market surveillance or inspections by third parties please consider the following warnings to reach the declared performance levels the product must perf...

Страница 8: ...e following causes Damage caused during transportation and or handling all parts that develop faults due to negligence or improper use incorrect maintenance installation that does not comply with the...

Страница 9: ...armaintenance The company declines all liability if the product and any other accessory is used improperly or modified without authorisation Allpartsmustbereplacedwithoriginalspareparts Information fo...

Страница 10: ...orsfuelledbywoodorothersolidbio fuels Test installation controlandmaintenance forthermochemical power at the firebox lower than 35kW UNI TS 11278 general technical regulation for the choice of smoke d...

Страница 11: ...that of pellets is around 4 9 kW kg To ensure good combustion the pellets must be stored in a dry place and protected from dirt Pellets are usually supplied in 15 kg bags therefore storing them is ver...

Страница 12: ...furniture andwithgoodaircirculation to allow effective ventilation for the appliance The product should be located in an area that allows sufficient space for normal use and maintenance operations The...

Страница 13: ...rements Increase the cross section by at least 6 cm2 for each 1 kW 859 64kcal h The minimum cross section of the opening must not however measure less than 100 cm2 The cross section can be calculated...

Страница 14: ...h performance have cooler fumes with consequently weaker draught and the possible formation of condensation It is therefore essential that the flue meets all construction standards and is always maint...

Страница 15: ...heck on the data tags of the flue in accordance with EN1856 1 EN1443 the safety distances that must be respected in presence of passing combustible materials and the type of insulating material to be...

Страница 16: ...50 metres D 0 50 metres ABOVE HIGHEST POINT E 0 80 metres F REFLUX AREA FIGURE 4 A MIN 2 60 metres B DISTANCE 1 20 metres C DISTANCE 1 20 metres D 0 50 metres ABOVE HIGHEST POINT E 2 10 metres F REFL...

Страница 17: ...the chimneys shown in the technical data tables are indications for correct installation Any alternative configurations must be correctly sized in accordance with the general method of calculation of...

Страница 18: ...CHIMNEYPOT Thechimneypotisacrucialelementfortheheatingappliancetoworkproperly werecommendawindproofchimneypot A seeFigure7 The area of the opening for smoke extraction must be at least double the cro...

Страница 19: ...hstand the high operating temperatures of the appliance min T200 class P1 The use of flexible metal hoses made of fibre cement or aluminium is forbidden For direction changes we always recommend the u...

Страница 20: ...afety distances from combustible materials The previous rules also apply for holes made in walls 2 Oldflue minimumtube 150mmwiththeinclusionof an external access door for chimney cleaning 3 External f...

Страница 21: ...18 5 100 1320 816 100 80 486 428 5 149 250 19 3 DRAWINGS ANDTECHNICAL CHARACTERISTICS Technical Dept All rights reserved Reproduction prohibited DRAWINGS AND CHARACTERISTICS SELECTA 35Q S1 DIMENSIONS...

Страница 22: ...n and at Max 6 6 13 1 Recommended draught at Max power 0 10 mbar 10 Pa Recommended draught at Min power 0 05 mbar 5 Pa Smoke mass 17 7 g sec Tank capacity 100 litres 65 kg Type of pellet fuel Pellet d...

Страница 23: ...0 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 B FLOW RATE dm3 h A PRESSURE H...

Страница 24: ...r it has been tested in the factory Remove the cardboard remove the brackets that secure the boiler to the pallet as well as the polystyrene To remove the rear bracket fig 2 one must remove the three...

Страница 25: ...suitable lifting trolleys Pay particular attention to the door and its glass protecting them from mechanical knocks that would compromise their integrity The product must always be handled with care I...

Страница 26: ...or the purpose of cleaning maintenance etc must be 700 mm the minimum permissible distance between the back of the product and a wall must be 400 mm the minimum distance between the top of the product...

Страница 27: ...SASSEMBLY Technical Dept All rights reserved Reproduction prohibited FUMES EXHAUST AND COMBUSTION AIR INLET The boiler is fitted at the back with a pipe U 0100 mm for fumes exhaust and with a pipe E 0...

Страница 28: ...andoff Ifthedoorsareopenedwhiletheboilerisrunning asystemwilltriggerthealarmandtheboilerwillgooff Open the outer door F by grasping the handle at the top right g and pull towards you Open the internal...

Страница 29: ...LY Technical Dept All rights reserved Reproduction prohibited ACCESSTOTHE ELECTRONIC BOARD To have access to the electronic board you must remove the right decoration panel door opening side according...

Страница 30: ...he selected hydraulic kit Remove cover R by loosening the two upper screws and lifting the cover so as to release the joint u of the cover from the v joint of the boiler REAR PANEL REMOVAL For interve...

Страница 31: ...9 C x x 29 6 INSTALLATION AND DISASSEMBLY Technical Dept All rights reserved Reproduction prohibited SIDE PANEL REMOVAL To remove the side panels proceed as follows At the rear remove the two screws x...

Страница 32: ...30 F C w C 30 6 INSTALLATION AND DISASSEMBLY on the front open the decorative door F remove the two screws w...

Страница 33: ...31 C C v k 31 6 INSTALLATION AND DISASSEMBLY Technical Dept All rights reserved Reproduction prohibited lift panel C so that hook k comes out from slot v on the boiler s structure...

Страница 34: ...DUEANDDEPOSITS Upstream from the boiler always install shutters so as to disconnect it from the plumbing system should it be necessarytomoveit orwhenitrequiresroutineand orspecialmaintenance Connect t...

Страница 35: ...ical Dept All rights reserved Reproduction prohibited CONNECTION WITH HYDRAULIC KIT FOR DOMESTIC HOT WATER PRODUCTION DIAGRAM SEE ACCESSORY CODE 40A18014 2 SAFETYVALVE 5 DOMESTIC HOTWATER INLET 3 FILL...

Страница 36: ...n withstand a temperature of 110 C not supplied and that reaches the outside via an anti odour syphon This drain is provided in order to prevent overpressures if the safety valve is opened The product...

Страница 37: ...pressure of the system while cold and the pre inflation pressure of the expansion tank must be the same In open vessel heating systems direct contact between circulating liquid and air is allowed Dur...

Страница 38: ...ature ifthisisnotthecase usethetaptofillthesystem Thisoperationmustbeperformedwhenthesystemiscool Thepressuregaugeonthesystemenablesyoutoreadthepressureinthecircuit During this operation any air in th...

Страница 39: ...condensation The prolonged formation of condensation causes permanent damage to the heat exchanger A higher return temperature reduces the formation of condensation of the fumes and extends the life...

Страница 40: ...r The pressure adjustments are made through the vent valve G at the top of the boiler see instructions on the previous page Low boiler pressure When the pressure of the boiler is too low and therefore...

Страница 41: ...or damp parts of the body and or when barefoot do not pull on the electrical cables do not expose the appliance to the elements rain sun etc do not allow children or inexperienced persons to use the...

Страница 42: ...outer or other device to activate theWPS Follow the procedure below Press the menu key scroll with the arrows until WiFi BLE is displayed confirm with Men scroll with the arrows and find WiFiWPS Press...

Страница 43: ...b Register a new user profile by pressing the REGISTER key entering your e mail address and creating a password c Ifrequired entertheconfirmationcodereceivedbye mailagua micronovasrl com don tforgetto...

Страница 44: ...IAWI FI on the configuration screen Navel Connection will appear 2 Close the app find theWi Fi settings on your smartphone and connect to the NAVEL_xxxxxx network Pay attention to any messages that ma...

Страница 45: ...you can choose what to display by pressing the menu key INFORMATION ADJUSTMENTS PROGRAMMABLETHERMOSTAT The items that can be displayed are The items that can be set are Youcansetupto6stoveoperating p...

Страница 46: ......

Страница 47: ......

Страница 48: ...REV 0 8902102600 18 01 2021 Via La Croce n 8 33074Vigonovo di Fontanafredda PN ITALY Telephone 0434 599599 a s Fax 0434 599598 Website www mcz it e mail info red mcz it...

Отзывы: