Description
3
BAL_FF_TWIN_EN_2V3_REC_121-006454269
17 / 38
3.4.6
Conduct during power failure (battery pack optional)
In the event of a power failure, the entrance door closes and locks while the exit door unlocks and
opens. The FlipFlow remains in this position until power is restored. This mode is only available when
the optional battery pack is selected.
Without battery, the FlipFlow stops in its current position and the doors can be opened manually.
FlipFlow-status
– Lighting and signal indicators are off.
– Entrance door closed and locked.
– Exit door open.
3.5
BMS information
It is possible to receive and transmit information to the FlipFlow BMS (Building Management System)
via dry contact relays. A rotary dial for selecting the operating mode in each vestibule installed is also
provided for controlling the FlipFlow from a distance.
3.5.1
Instructions sent from the BMS
An emergency opening command, with absolute priority.
An emergency close command, closes and locks the entrance door and opens the exit door, priority
over operating modes.
Switches manually to FLOW mode if INTERLOCK mode has been selected locally and vice versa.
This function depends on the passenger flow.
3.5.2
Information received by the BMS
An intrusion alarm has been detected.
An anti-pass-back alarm has been detected.
An object or a person has been located in the detection zone of the vestibule for a long period of time.
An object or a person has been located in the detection zone of presence and is blocking the pas-
sage, or a FlipFlow electrical component is defective.
Provides information about the position of the entrance door: closed or locked.
Indicates that there are no alarms, the FlipFlow is working properly: passengers can pass through.
Indicates that a person is working on the FlipFlow, or that it is in no alarm mode.
Indicates that the maintenance hatch is open.
Indicates that the emergency open button has been activated; requires a manual reset.
The FlipFlow is being cleaned.
Provides information about the position of the exit door: closed or locked.
Indicates the state of the power supply.
The FlipFlow is in FLOW mode.
The FlipFlow is in OPEN mode.
The FlipFlow is in LOCKED mode.
The FlipFlow is in INTERLOCK mode.
NOTICE
Configurable:
a) Logic information (No/Nc)
b) Information about the doors positions