DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3
Page 102
PAGE 1
BOILER MODE
AUTO
AUTO, LOCAL,
COMBINATION
Setting this value to LOCAL or COMBINATION enables the DHW
PID. Setting this value to AUTO disables the DHW PID.
LOCAL
allows the boiler to run in DHW locally off of its own
sensor or thermostat input. The boiler could be configured to run as a
space heating boiler that is controlled by a Master. It would also
monitor a tank or DHW call and disconnect from the Master to
provide local DHW heat.
COMBINATION
allows the boiler to be configured to run as a
space heating boiler and a DHW boiler that is controlled by a Master.
This would use both the space heating PID and the DHW PID to
simultaneously control space heating and DHW heating.
NO, turns off the DHW PID, but still allows control of the DHW
pump and DHW setpoint for backwards compatibility.
*Note: If the System is configured to use the OR OVR input to
override the heating setpoint with the DHW setpoint, the DHW PID
is not used. Since this method does not use the DHW PID, the DHW
BOILER setting should be set to NO. The DHW SETPOINT, POST
PURGE, LOCAL PUMP OFF, LOCAL DELAY, and PURGE TO
THE: may need to be set if this method is used. This method does
allow configuring the LOCAL and DHW pumps.
SETPOINT
160
°
F
40
– 200 °F
Setpoint that the boiler/system will target when a call for DHW.
LOWER BAND
5
°
F
1
– 30 °F
DHW SETPOINT – LOWER DHW DIFF: if the DHW water
temperature is less than this temperature, the Boiler/System will
enter DHW Heating mode if DHW BOILER? is set to LOCAL or
MIXED or COMBINATION.
UPPER BAND
3
°
F
1
– 30 °F
DHW SE UPPER DHW DIFF: if the DHW water
temperature is greater than this temperature, the Boiler/System will
begin shutting off DHW boilers if the DHW BOILER? is set to
LOCAL or COMBINATION.
PUMP PRIORITY
NO
If the DHW PRIORITY is set to YES, then when there is a call for
DHW, the system pump shuts off. If NO, the system pump stays on.
POST PURGE
120 Seconds
5-600 Seconds
This is the time that the DHW relay remains on after the DHW call
ends.
USE SENSOR
NO
If this entry is set to YES, the DHW 10k Sensor is looked to for
controlling DHW water temperature. If set to NO, A thermostat is
used.
SHARING
CYCLE
OFF, NO CYCLE,
CYCLE
NO CYCLE
allows the boiler to perform as a space or DHW heating
boiler. DHW always has priority and will override (steal) a space
heating boiler that is running when none are available to perform
DHW heating. When this happens, the boiler will not shut down, but
keep running during the change from space heating to DHW (Hot
Swap). Once the DHW cycle completes, the boiler will shut down
and wait to be called for space heating again.