MODBUS COMMUNICATIONS
HeatNet Control V3
Page 121
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
30088
Boiler09Status3
30089
Boiler10Status3
30090
Boiler11Status3
30091
Boiler12Status3
30092
Boiler13Status3
30093
Boiler14Status3
30094
Boiler15Status3
30095
Boiler16Status3
----- The following registers are available starting in firmware version 2.0 -----
30096
Boiler01SupplyTemp
16 bit signed
0.01
Boiler (1
– 16) supply temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32
– 250 °F
30097
Boiler02SupplyTemp
30098
Boiler03SupplyTemp
30099
Boiler04SupplyTemp
30100
Boiler05SupplyTemp
30101
Boiler06SupplyTemp
30102
Boiler07SupplyTemp
30103
Boiler08SupplyTemp
30104
Boiler09SupplyTemp
30105
Boiler10SupplyTemp
30106
Boiler11SupplyTemp
30107
Boiler12SupplyTemp
30108
Boiler13SupplyTemp
30109
Boiler14SupplyTemp
30110
Boiler15SupplyTemp
30111
Boiler16SupplyTemp
30112
Boiler01ReturnTemp
16 bit signed
0.01
Boiler (1
– 16) return temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32
– 250 °F
30113
Boiler02ReturnTemp
30114
Boiler03ReturnTemp
30115
Boiler04ReturnTemp
30116
Boiler05ReturnTemp
30117
Boiler06ReturnTemp
30118
Boiler07ReturnTemp
30119
Boiler08ReturnTemp
30120
Boiler09ReturnTemp
30121
Boiler10ReturnTemp
30122
Boiler11ReturnTemp
30123
Boiler12ReturnTemp
30124
Boiler13ReturnTemp
30125
Boiler14ReturnTemp