OPTIONAL FEATURES
HeatNet Control V3
Page 66
To maintain a minimum flow through the boiler, the “Flow
Prove: GPM” is adjustable. Enter the minimum flow that the
boiler is to prove and operate above, then select “OK”.
When the boiler has a heat demand it will not start until the
programmed GPM requirement is met. If the boiler is
running, it will also stop firing when the GPM falls below the
Flow Prove value. In this case the minimum flow is below
the required 16 GPM so the boiler will not start. The flow
proof time has expired and then enters a fault condition.
The touchscreen displays a visual flow fault, and the control
will annunciate an audible fault. After ten minutes, if the
demand is still present, the boiler will retry to start the pumps
to achieve flow and start the boiler. If there are other boilers
on the network the Master will attempt to start one of them.
Security
A password can be used to lock out control and setup features.
It can be enabled but is shipped in the disabled state.
Save/Restore Configuration
Settings
In a complex system, there can be a multitude of settings
necessary for proper boiler operation. These settings can be
saved to the onboard memory, and/or a USB drive. SAVE
SETTINGS: ONBOARD MEMORY/USB FILE