DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3
Page 99
Flow Factor
PPG
Currently not used.
SYSTEM
BOILER TYPE
CONFIGURE INTERLKS
The 24 VAC interlocks can be enabled or disabled for reporting.
LOAD FIRMWARE
NO
Enters the Load Firmware menu. Loading new firmware allows for
upgrades and bug fixes to the HeatNet control. Check the
http://www.rbiwaterheaters.com/
website periodically for updates.
SOURCE
USB DRIVE
USB DRIVE,
USB CABLE,
SAVE FILE
Selecting
USB DRIVE
will read the FIRMWARE directory on a
flash drive and display any .hex files located there. Follow the on
screen prompts and then select a file using the arrow keys. Once a
file has been selected, a STORAGE LOCATION needs to be
selected. There are (2) storage locations for the new file. Location 1
is used for normal updates and Location 0 is for the factory stored
backup file. When the Storage location (default is Location 1) is
selected the file will be loaded into a permanent storage memory
location. Next, the control will reboot and copy this new program
into running memory, reboot, load factory defaults, and then reboot
again.
Selecting
USB CABLE
requires
connecting a USB cable and
running the Firmware Update program from a PC. This process
takes longer and requires a Personal Computer (laptop) to be taken
to the boiler site. Again, follow the on screen prompts to down load
the program into a storage location as done when using the above
USB DRIVE loading menu.
Selecting
SAVE FILE
will display the currently stored files in the
storage memory locations. Use the arrow keys to select a stored file
for copying to running memory. When
SELECT
is pressed the file
will be marked so it will be loaded on the next power cycle. Power
cycle the boiler to begin copying the file from stored memory to
running memory.
NOTE:
to access the factory backup program, the shunt on the
control needs to be connected and the CAL/NORMAL P3 BOOT
switch placed in the CAL position. If the control is power cycled in
this condition, the factory program will overwrite the existing
running program. If in the LOAD FIRMWARE menus, STORAGE
LOCATION 0 will be an allowed storage location. When the
backup program begins to load, remove the shunt on P3 and place
the CAL switch back to normal.
OPTION:
NO OPTION
NO OPTION
DUAL FUEL
BASE LOAD
When set to DUAL FUEL, input T3/ RESERVED, OPTION input
is used to control the DUAL FUEL OPTION relay via K8 contacts
on J4.2 &.6. When set to NO OPTION the input T3/RESERVED,
OPTION relay K8 on J4.2 &.6 is inactive.
When set to BASE LOAD, the Option Relay K8 on J4.2 &.6 is used
as an enable contact for a base load boiler. The J4.1 &.5 0-10vdc/4-
20mA output is used to modulate the base load relay if it is of the
modulating type.
BOILER TYPE
PRODUCT:
MB/MW 500
MB/MW 500 -
MB/MW 5000
The product type allows configuration of the control. The following
fields will be adjusted to the default for the product.
CONDENSING
YES
This defines a boiler as condensing or non-condensing. This value is
not used with this version and is displayed only for reference and
future applications.
BTU IN
200,000
This is the BTU input rating of the boiler. This value is not used
with this version and is displayed only for reference.
BLOWER
VFD
VFD
This is the blower type associated with the product. This should not
be changed manually.
Содержание FUTERA XLF Series
Страница 21: ...SETUP OPERATION HeatNet Control V3 Page 21 Figure 17 Mixed Boilers Example Condensing Non Condensing...
Страница 27: ...CONTROL METHODS HeatNet Control V3 Page 27 Figure 25 Base loading relay...
Страница 67: ...WIRING CONNECTIONS HeatNet Control V3 Page 67 Figure 49 Jumper Dip Switch Locations...
Страница 73: ...WIRING CONNECTIONS HeatNet Control V3 Page 73 Figure 57 Temperature sensors...
Страница 125: ...WORKSHEET HeatNet Control V3 Page 125 TURNDOWN ALTITUDE CALIBRATION SETTINGS MIN VFD IGN VFD MAX VFD...
Страница 127: ...413 568 9571 Fax 413 568 9613 Page 127...