MODBUS COMMUNICATIONS
HeatNet Control V3
Page 111
BoilerStatus4 Flags
Bit
Description
Valid Values/Range
0
DHW Enabled (1)
DHW Mode had been enabled in the menus.
0 = off, 1 = on (menu)
1
Combustion Air Damper Prove (1)
Status of Combustion Air Damper Prove Input J12B
0 = not proven, 1 = proven
2
Call Service Fault
0 = off, 1 = on
3
Air Switch (Blower) Fault
0 = off, 1 = on
4
---
---
5
---
---
6
---
---
7
---
---
8
---
---
9
DHW Sensor not detected (1)
0 = detected, 1 = not detected
10
DHW Boiler (1)
This control board has been designated a DHW boiler by cutting the DHW
jumper (JPS1).
0 = no, 1 = yes (DHW jumper cut)
11
Operating Limit Clamp (1)
Boiler input is being limited (clamped) due to a high supply (outlet)
temperature.
0 = off, 1 = clamped
12
Firing boilers limited by value in BMS Flow Rate Register (1)
0 = not limited, 1 = limited
13
Firing boilers limited by value in BMS Limit Boilers Register (1)
0 = not limited, 1 = limited
14
Stack Sensor not detected (2)
0 = detected, 1 = not detected
15
System Return Sensor not detected (2)
0 = detected, 1 = not detected
(1) Available in firmware version 1.30+.
(2) Available in firmware version 2.00+.
Содержание FUTERA XLF Series
Страница 21: ...SETUP OPERATION HeatNet Control V3 Page 21 Figure 17 Mixed Boilers Example Condensing Non Condensing...
Страница 27: ...CONTROL METHODS HeatNet Control V3 Page 27 Figure 25 Base loading relay...
Страница 67: ...WIRING CONNECTIONS HeatNet Control V3 Page 67 Figure 49 Jumper Dip Switch Locations...
Страница 73: ...WIRING CONNECTIONS HeatNet Control V3 Page 73 Figure 57 Temperature sensors...
Страница 125: ...WORKSHEET HeatNet Control V3 Page 125 TURNDOWN ALTITUDE CALIBRATION SETTINGS MIN VFD IGN VFD MAX VFD...
Страница 127: ...413 568 9571 Fax 413 568 9613 Page 127...