TROUBLESHOOTING
HeatNet Control V3
Page 115
Situation:
We are using a BACnet or LonWorks bridge. We
can talk to the bridge, but all of the data is zero (0)
or invalid.
This condition usually indicates that the bridge is not
communicating with the HeatNet control. When operating
properly, the bridge continuously reads data from the boiler
on the Modbus port into an internal buffer. When a BACnet
or LonWorks read request is received, the buffered values
are placed in a BACnet or LonWorks packet and sent. If the
bridge has never been able to successfully read data from
the control, all data points will have their default value
which is typically zero. In this situation, the control will also
not respond to write commands; for instance changing the
setpoint.
1.
The control’s
MODBUS ADDRESS
must be set to one
(1). This is set in the
ADVANCED SETUP-
>DISTRIBUTED CONTROL
menu. On older
(legacy) firmware this setting was also called the
CONSOLE ADDRESS
.
2.
The control’
BAUD
(rate) must be set to 19200 and the
DATA FORMAT
must be set to
8E1
(8 data bits, even
parity, 1 stop bit). On older (legacy) versions of
firmware, the
DATA FORMAT
was called
PARITY
which must be set to
EVEN
. These settings are set in
the
ADVANCED SETUP->COMMUNICATIONS
menu.
3.
Check the termination on the BMS/Modbus port. If the
control is the first or last device on the Modbus RTU
network, it should be terminated. For the short cable
runs (for instance when using a BACnet or LonWorks
bridge on a Revision 1.x board), the termination should
be in, but usually doesn’t matter.
4.
Check the wiring. The Modbus RTU (RS485)
connections on the HeatNet control are A(+), B(-), and
G (ground). Some systems use opposite polarity; A(-),
B(+). Always use the polarity to determine the proper
connections.
A ground wire must always be used
and a shielded twisted wire is STRONGLY
suggested.
5.
The HeatNet LonWorks and BACnet bridges plug
directly into Revision 2.x+ boards. Legacy boards
(Revision 1.x) required a ProtoCarrier to provide power
and the RS485 signal conversion to the bridge. The
RS845 signal conversion chips are easily damaged by
electrical noise, ground loops, and large differences in
ground potential between devices on the network. This
is a common problem faced by all RS485 devices, not
just the HeatNet control. To help eliminate grounding
problems, nylon standoffs are required to isolate the
bridge from the boiler chassis. The ProtoCarrier should
also be powered from the 24VDC output on the
HeatNet control to help eliminate electrical noise (VFD
and spark pickup, power spikes, etc.) on the power
supply lines. Please download complete HeatNet
bridge installation instructions from the product web
site.
a.
When the ProtoCarrier is functional, the small
green surface mount TX and RX LEDs near the 6-
pin connector (power and communications) should
be flashing regularly.
b.
If the TX LED flashes very briefly about once per
minute, the ProtoCarrier has most likely been
damaged, please contact Tech Services.
c.
If either LED is always on, the ProtoCarrier has
most likely been damaged, please contact Tech
Services.
Situation:
We are using a Building Management System
(BMS) to control the boilers. We can write the
setpoints, but they keep changing back to their
“default” values after approximately 60 seconds.
1.
When using a BMS, the setpoint values work in
conjunction with the
SETPOINT TIMER
. The
SETPOINT TIMER
is a failsafe feature used to help
detect that a BMS is no longer working or
communicating with the control. The time must be
regularly loaded with a predetermined number of
seconds (1 – 65535). Every second this value will
decremented. If it reaches zero, the local (permanently
saved) values for the setpoints will be loaded. The
concept is that periodically (or every time a setpoint is
written), the BMS must write this value. If the value
reaches zero (0), the HeatNet control assumes that the
BMS in no longer functional and “safe” operational
values for the setpoints will be restored. As an
example, if it is decided that the BMS will write the
control every 5 minutes, you may decide to write 600
seconds (10 minutes) to the setpoint timer. If after 10
minutes (5 minutes longer than the normal write
interval) the BMS has not written the timer, the saved
setpoint values will be restored.
2.
As a convenience, the
SETPOINT TIMER
is
automatically loaded with 60 seconds (if it has fallen
below 60) each time the setpoint is written. If you
decide to take advantage of this convenience, you
would need to write the setpoint periodically at less
than 1 minute intervals. This value can be adjusted up
to 4 hours (instead of 60 seconds) using the
ADVANCED SETUP->COMMUNICATIONS
SETPT TIME
> menu.
Содержание FUTERA XLF Series
Страница 21: ...SETUP OPERATION HeatNet Control V3 Page 21 Figure 17 Mixed Boilers Example Condensing Non Condensing...
Страница 27: ...CONTROL METHODS HeatNet Control V3 Page 27 Figure 25 Base loading relay...
Страница 67: ...WIRING CONNECTIONS HeatNet Control V3 Page 67 Figure 49 Jumper Dip Switch Locations...
Страница 73: ...WIRING CONNECTIONS HeatNet Control V3 Page 73 Figure 57 Temperature sensors...
Страница 125: ...WORKSHEET HeatNet Control V3 Page 125 TURNDOWN ALTITUDE CALIBRATION SETTINGS MIN VFD IGN VFD MAX VFD...
Страница 127: ...413 568 9571 Fax 413 568 9613 Page 127...