DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3
Page 100
MASS
MEDIUM
LOW,MEDIUM, HIGH
This defines the mass of the boiler. This value is not used with this
version and is displayed only for reference and future applications.
TURNDOWN
5:1
3:1, 4:1, 5:1
This is the turndown of the boiler. For the Futera III/Fusion-Series
the default is 5:1 and determines the minimum firing percentage.
5:1 = Min 20%, 4:1 = Min 25%, 3:1 = Min 33%.
NOTE: The boiler must be set up for operation at this Turndown
rate using the Calibrate settings. This TURNDOWN setting only
controls the displayed percentage.
ALTITUDE
< 2000FT
< 2000 FT,
> 2000 FT,
> 4000 FT
This is the Altitude in feet of where the boiler is installed. On some
Blowers it limits the blower output for low altitudes and allows a
higher output at higher altitudes. Currently, this setting is not used
on the Futera III/Fusion-Series boilers.