72
Register
Parameter
Read/Write
Format
Note
Register Address
Boiler 3 Status
Registers
.
MODBUS = MNTR or
TEMP
Boiler3 detected
R
S16
"0 = boiler not
detected, 1 = boiler
detected"
74
Boiler3 On/Off
R/W
S16
"0 = offline, 1 =
online"
1030
Boiler3 Outlet
temperature
R
S16
75
Boiler3 Inlet
temperature
R
S16
76
Boiler3 Vent
temperature
R
S16
77
Boiler3 High Limit
temperature
R
S16
78
Boiler3 Operator
temperature
R
S16
79
Boiler3 Mod
Rate
R
S16
0-100%
80
Boiler3 Mix Rate
R
S16
not available in initial
release
81
Boiler3 Ignition
Status
R
S16
82
Boiler3 Runtime
R
S16
83
Boiler3 Cycles
R
S16
84
Boiler3 Pump
R
S16
85
Boiler3 Pump
Runtime
R
S16
86
Boiler3 Error
Code
R
S16
87
Boiler3 Error
History 1
R
S16
88
Boiler3 Error
History 2
R
S16
89
Boiler3 Error
History 3
R
S16
90
Boiler3 Error
History 4
R
S16
91
Boiler3 Error
History 5
R
S16
92
Boiler3 Error
History 6
R
S16
93
Boiler3 Error
History 7
R
S16
94
Boiler3 Error
History 8
R
S16
95
Boiler3 Error
History 9
R
S16
96
Boiler3 Error
History 10
R
S16
97
Boiler3 Error
History 11
R
S16
98
Boiler3 Error
History 12
R
S16
99
Boiler3 Error
History 13
R
S16
100
Boiler3 Error
History 14
R
S16
101
Boiler3 Error
History 15
R
S16
102
reserved
Table Y: Boiler 3 Status Registers
Содержание 5000.72A
Страница 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual ...
Страница 28: ...28 Fig 26 WH Direct DHW single Heater with CWP VS Pump MIX TYPE 2 Fig 25 WH Direct DHW Single Heater ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...80 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 9725 Litho in U S A ...