67
10K Sensor Resistance Values
Temperature (
°
F)
Resistance (Ω)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
203
786
212
667
Resetting PIM™
Should it be necessary to move a PIM™ control to
another heater, the PIM™ has to be reset to allow the
ID Card to unlock the appropriate program parameters
and to load them into the PIM™ memory.
Follow these steps for a hard reset of the PIM™ to
clear program parameters:
1. Remove power from the PIM™ control.
2. Set all DIP switches on the PIM™ to their OFF
position.
3. Unplug connector J6 on the PIM™ control.
4. Unplug VERSA
®
CAT 5 cable from PIM™ control.
5. Press and hold the reset/test button (located next
to the LEDs on the right side of the PIM™ board)
while powering the controller for 5 seconds.
6. The red diagnostic LED will flash indicating a suc-
cessful reset. The PIM™ board’s memory is now
clear of any ID Card parameters.
7. Release the reset/test button.
8. Remove power from the PIM™ control.
9. Connect connector J6 to the PIM™ control.
10. Power up the PIM™ control.
11. If the reset was successful, the green LED shows
steady ON.
12. If the red and yellow LEDs are ON and the green
LED is OFF, the reset was NOT successful.
13. If the reset was not successful, repeat steps 1-11.
14. If reset was successful, remove power and reset
DIP switches for desired operation and return the
unit to operation.
15. Restore VERSA
®
to default values, be aware that
all configuration will be reset. Verify user settings
as necessary.
CAUTION:
DO NOT
swap a PIM™ from 1 heater to
another heater without resetting the PIM™ as out-
lined below.
Table T: 10K Sensor resistance values
Restoring VERSA
®
to
factory defaults
To restore the VERSA
®
control to factory default set-
tings do the following.
1. Using the MENU button scroll to the TOOLBOX
menu.
2. Use the ITEM button and scroll until you reach the
DEFAULTS screen.
3. Press and hold the UP and DOWN arrow buttons
simultaneously until CLR appears on the screen.
The VERSA
®
has been returned to factory default set-
ting. Press the MENU button to return to the ADJUST
menu and set the controller for the desired functional-
ity.
Содержание 5000.72A
Страница 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual ...
Страница 28: ...28 Fig 26 WH Direct DHW single Heater with CWP VS Pump MIX TYPE 2 Fig 25 WH Direct DHW Single Heater ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...80 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 9725 Litho in U S A ...