71
Register
Parameter
Read/Write
Format
Note
Register Address
Boiler 2 Status
Registers
.
MODBUS = MNTR or
TEMP
Boiler2 detected
R
S16
"0 = boiler not
detected, 1 = boiler
detected"
45
Boiler2 On/Off
R/W
S16
"0 = offline, 1 =
online"
1029
Boiler2 Outlet
temperature
R
S16
46
Boiler2 Inlet
temperature
R
S16
47
Boiler2 Vent
temperature
R
S16
48
Boiler2 High Limit
temperature
R
S16
49
Boiler2 Operator
temperature
R
S16
50
Boiler2 Mod
Rate
R
S16
0-100%
51
Boiler2 Mix Rate
R
S16
not available in initial
release
52
Boiler2 Ignition
Status
R
S16
53
Boiler2 Runtime
R
S16
54
Boiler2 Cycles
R
S16
55
Boiler2 Pump
R
S16
56
Boiler2 Pump
Runtime
R
S16
57
Boiler2 Error
Code
R
S16
58
Boiler2 Error
History 1
R
S16
59
Boiler2 Error
History 2
R
S16
60
Boiler2 Error
History 3
R
S16
61
Boiler2 Error
History 4
R
S16
62
Boiler2 Error
History 5
R
S16
63
Boiler2 Error
History 6
R
S16
64
Boiler2 Error
History 7
R
S16
65
Boiler2 Error
History 8
R
S16
66
Boiler2 Error
History 9
R
S16
67
Boiler2 Error
History 10
R
S16
68
Boiler2 Error
History 11
R
S16
69
Boiler2 Error
History 12
R
S16
70
Boiler2 Error
History 13
R
S16
71
Boiler2 Error
History 14
R
S16
72
Boiler2 Error
History 15
R
S16
73
reserved
Table X: Boiler 2 Status Registers
Содержание 5000.72A
Страница 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual ...
Страница 28: ...28 Fig 26 WH Direct DHW single Heater with CWP VS Pump MIX TYPE 2 Fig 25 WH Direct DHW Single Heater ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...80 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 9725 Litho in U S A ...