64
Error Message
Description
Recommended Troubleshooting
OUTLET SEN
Heater outlet sensor fault
Check outlet sensor
Check outlet sensor wiring
LIMIT SEN
High limit sensor fault
Check limit sensor
Check limit sensor wiring
INLET SEN
Heater inlet sensor fault
Check inlet sensor
Check inlet sensor wiring
VENT SEN
Vent sensor fault
Check vent sensor
Check vent sensor wiring
INTERLOCK
Factory installed jumper in place when shipped.
Check louver end switch & wiring
Check combustion air damper end switch & wiring
Check extractor & wiring
WATER PRESS
Water pressure switch fault (if equipped) – Raypak
factory installed jumper in place if not shipped with
water pressure switch
Verify wiring at J1 terminals 6 & 7
Check heater pump
Check isolation valves
AIR PRESS
Air pressure switch fault (if equipped) – Raypak factory
installed jumper in place if not shipped with air
pressure switch
Verify wiring at J8 terminals 2 & 4
Check blower(s)
Check air pressure switch tubing
GAS PRESS
Gas pressure switch fault (if equipped) – Raypak
factory installed jumper in place if not shipped with high
pressure switch and/or low gas pressure switch
Verify wiring at J8 terminals 1 & 3
Check gas pressure switches
Check gas pressure
Check gas pressure switch tubing
IGNITION
Ignition fault
Reset ignition control – Push either
RESET
button on membrane
switch or reset button on PIM™ or recycle power
LIMIT TRIP
Boiler outlet temperature tripped the high limit
Push reset button on high limit control if Manual Reset High Limit
tripped
Wait for water temperature to drop and auto reset high limit will reset
Check pump operation
Check bypass (if equipped) for too much water flow
FLAME
Flame detected without call for heat
Shut off gas supply
Recycle power
Check gas valve leakage
ID CARD
Invalid/missing ID Card
Connect ID Card mounted in heater
Contact the factory if “Invalid ID Card” is noted
IGN CTRL
Internal PIM™ control fault
Recycle power – if error continues to occur, replace PIM™
DELTA T
Threshold Delta T temperature exceeded
Check pump operation
Check Delta T setting
Check bypass (if equipped) for too much water flow
LO HSI CUR
Low HSI current at PIM™ control
Check HSI current
Replace HSI
Replace PIM™ control
LOW 24VAC
Low 24VAC power at PIM™ control
Check power supply
Check transformer
BLOW SPEED
Blower speed (rpm) out of range
Check power supply
Check blower wiring to PIM™
Check blower type
SAFETY INPUT
Additional factory installed safety fault – see Product
I&O manual for specific information relating to this
Verify wiring at J8 – terminals 5 & 6
Table Q: Error messages generated from the PIM™ but displayed on the VERSA IC
®
Display
Содержание 5000.72A
Страница 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual ...
Страница 28: ...28 Fig 26 WH Direct DHW single Heater with CWP VS Pump MIX TYPE 2 Fig 25 WH Direct DHW Single Heater ...
Страница 78: ...78 ...
Страница 79: ...79 ...
Страница 80: ...80 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 9725 Litho in U S A ...