prior to working with any electrical connections or
components.
3.
Observe proper wire colors while making electri-
cal connections. Many electronic controls are
polarity sensitive. Components damaged by
improper electrical installation are not covered by
warranty.
4.
Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.
5.
Install heater controls, thermostats, or building
management systems in accordance with the
applicable manufacturers’ instructions.
6.
Conduit should not be used as the earth ground.
Field Wiring Connection
22
NOTE:
A grounding electrode conductor shall be
used to connect the equipment grounding
conductors, the equipment enclosures, and the
grounded service conductor to the grounding
electrode.
Fig. 18: Wiring Location
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is discon-
nected to avoid potential serious injury or damage to
components.
CAUTION:
Label all wires prior to disconnection
when servicing controls. Wiring errors can cause im-
proper and dangerous operation. Verify proper
operation after servicing.
Fig. 19: On-Off Wiring Connections
Содержание 399B-2339B
Страница 23: ...23 Fig 20 2 Stage Wiring Connections Fig 21 3 Stage Wiring Connections Fig 22 4 Stage Wiring Connection...
Страница 39: ...Wiring Diagram Models 399B 1259B 39...
Страница 40: ...Wiring Diagram Models 1529B 2339B 40...
Страница 52: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...