The optional single-try ignition module will lock out
after failing to light one time. To reset it, press and
release the small, recessed black push button located
inside of the cut-out on the lower right-hand corner of
the ignition module case (see Fig. 28). Turning off the
power to the heater WILL NOT reset the ignition mod-
ule.
High Limit (Manual Reset)
The heater is equipped with a manual reset high limit
temperature device. Push the reset button and adjust
the setting to 40 - 50°F above desired operating tem-
perature.
Flow Switch
This dual-purpose control, mounted and wired in
series with the main gas valve, shuts off heater in case
of pump failure or low water flow.
Operating Control
The heater may be equipped with different types of
operating controls. Consult the individual control data
Fig. 29: High Limit (Manual Reset)
Fig. 30: Flow Switch
Ignition Module
When additional heat is needed, the combustion air
blower starts to purge air from the combustion cham-
ber for about 15 seconds. On proof-of-air flow, the air-
proving switch closes and the igniter is energized. To
ensure safe operation, the gas valve cannot open until
the igniter is verified. The main burner is automatically
lit when the device is powered and pre-purged. The
heater performs its own safety check and opens the
main valve only after the igniter is proven to be capa-
ble of ignition.
Code
Condition
On
System OK;
No faults present
Off
Possible control fault;
Check power
1 Flash
Low air pressure, brief
flashing normal on start-up
2 Flashes
Flame in combustion
chamber; No call for heat
3 Flashes
Ignition lockout
4 Flashes
Low igniter current
5 Flashes
Low 24 VAC, check control
supply voltage
6 Flashes
Internal fault;
Replace module
Fig. 28: Ignition Module
Table O: Ignition Module Diagnostic LED Codes
connection close after 5 seconds.
56. The stage 4 temperature controller contacts close.
57. Power is sent to gas valve 4.
58. The heater is now operating at full fire.
The standard ignition module will attempt to light three
times before locking out. To reset it, turn off power to
the heater, wait 30 seconds and re-apply power.
Reset button
on 1-try
module
Содержание 399B-2339B
Страница 23: ...23 Fig 20 2 Stage Wiring Connections Fig 21 3 Stage Wiring Connections Fig 22 4 Stage Wiring Connection...
Страница 39: ...Wiring Diagram Models 399B 1259B 39...
Страница 40: ...Wiring Diagram Models 1529B 2339B 40...
Страница 52: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...