Table 1 shows wire sizes larger than #10 (the maximum that fits the MT5 Module
connectors). If #10 AWG wire is too small to avoid excessive voltages drops, larger wire
can be used by transitioning from the larger wire to a #10 wire near the Multi-Tracer
load unit. For example, by mounting a terminal block near the load unit.
Aux Input Connections
The Multi-Tracer uses a 3-pin connector for each auxiliary (Aux) input. These are
typically used for pyranometers but may be used for any DC voltage signal within the
input range of +/- 5V.
The connector and each pin function is shown in Figure 6.
(1)
Signal - (2)
GND/Shield (3)
Figure 6. Multi-Tracer Aux input connector.
Note: The Multi-Tracer makes a differential measurement between the signal positive
and negative inputs. However, this signal must be referenced to the Multi-Tracer ground
(GND). If the signal source (pyranometer) does not reference to ground, then add a
reference to ground at this connector. For example, place a jumper from signal negative
to the GND connection.