IMPORTANT :Please, lubricate the
internal part of the seals before
being fitted.
18
TYPE OF FLUE SYSTEM (All models)
TABLE 6
Flue type C
13
C
33
C
53
1
Flue Diameter 60/100 80/125 60/100 80/125 80mm
(concentric) (concentric) (concentric) (concentric) single pipe
Minimum length (m) 0.3 0.3 1.0 1.0 0.5
(vertical length) (vertical length)
Maximum length (m) 8.0 23.0 13.0 26.0 43.0
Equivalent length of 45° bend (m) 0.5 1.25 0.5 1.25 1.25
Equivalent length of 90° bend (m) 1.0 2.5 1.0 2.5 2.5
OPTIONAL EXTRAS: (See Table 7)
HORIZONTAL FLUE KIT BOX CONTAINING (Fig 12)
57 - Flue bend assembly
59 - Rubber seal Ø 60
60 - Air intake duct
61 - Flue exhaust duct
62 - Terminal
127 - Terminal Rubber wall seal
Fig 14
Fig 12
WARNING
with horizontal concentric fl ue
Maximum allowable fl ue length 8 m
maximum No 7x1000 mm
Flue duct extension used with standard fl ue
FLUE EXTENSION BOX CONTAINING
(Fig. 14)
1000 mm fl ue extension duct as an extra cost only
when requested for side and vertical fl ue applications
59 - Rubber seal Ø 60
63 - Air intake duct extension
64 - Flue exhaust duct extension
Generally speaking,oils and greases are not
suitable for the “peroxide -EPDM”, therefo-
re we suggest a correct lubrication using
silicon-substances, for instance “Silikon
Spray“ (Arexons)or the same product from
the company “Soltecno s.r.l.”.