BOILER NOT OPERATIONAL ON TIMER (INTEGRAL)
Switch on/select “Winter” / Central heating.
Stat to Maximun/Ensure External control calling for heat (Room Stat / TRV).
Is Timer set to
“OFF” ?
Set Timer to Required
mode - Recheck
Yes
No
Yes
Yes
No
Yes
Yes
Yes
No
Timer set to
“AUTO” ?
No
No
No
Check programme are
setting Correct
Timer set to “ON” ?
Timer set to “AUTO”
Does neon on
Timer illuminate?
Are L and N connections
to points 1 and 2 ?
Yes
Is there 230V across
point 1 and 2 ?
Are L and N correctly ?
Electrical fault within
boiler ?
No
TIMER FAULT
With leads disconnected, is there
continuity across leads to 3 and 5 ?
Enter correct programme
as per instructions provided.
Recheck.
No
With leads connected, is there continuity
across leads to 3 and 5 ?
No
Is there continuity
across internal fuse ?
Change fuse
External Control fault - Check.
Yes
Electrical fault within
boiler.
Yes
41