- 13 -
V03 EN, Fundamentals
Center S2 ==> Ground:
2 - 6V AC:
water level too low
steam heating must switch OFF
solenoid valve filling Y1 ON
Center S2 ==> Ground:
0V AC:
water level reached
steam heating can switch ON
solenoid valve filling Y1 switched OFF
The level electrode is equipped with two side elec-
trodes to ensure a safe water level recognition even
though the level electrode is scaled. These side
electrodes compensate the build up of scale (CM).
Permanent water level control;
Maximum continous steam time: 2 Minutes,
Property of connected water:
Conductivity must be above 50μS/cm;
Overfilling of the steam generator can be caused by a
connected water treatment system.
St.Gen. empty: ca. 2 - 6V AC
St.Gen. empty: 0V
SV Filling on 230V
SV Filling off 0V
Heating on 230V
Heating off 0V
Filling SG
Max. heating 2 Min.
Control
Steam heating
V
AC
S2
M4
Y1
Y2
B2
S2
B5
F3
Water level control Steam Generator