59
● Output ON and OK or in Cold Redundant Slave mode(Green)
● AC present / only 12Vsb on (PS off)( 1Hz Blink Green)
● AC cord unplugged or AC power lost; with a second power supply in parallel still with AC input
power(AMBER)
● Power supply warning events where the power supply continues to operate high temp, high power, high
current, slow FAN.(1Hz Blink Amber)
● Power supply critical event causing a shutdown; failure, OCP, OVP, FAN fail. (Amber)
AC Power Cord
The AC power cord is located on the chassis rear side, not on the front (PSU) side. The AC
cord type at PS390E side is C14, and the power cable with USA and China power cord can
be chosen, so users can use system attached C13 to C14 power cable. Contact with
Rasilient for other options if want to use other types of power cord.
NOTE
: The PSU AC input range: 180 to 264V rms.
Figure 41: PSU Front View
Figure 42: AC Power Cord