B-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
138 of 147
22.3 Burner
PROBLEM
POSSIBLE CAUSE
SOLUTION
Flame control does not try for
ignition
A
u
xiliary contact "M1" not closed. Po
w
er on terminal
"4"?
Properly mo
u
nt contact or replace
B
u
rner/
w
inter s
w
itch closed? Po
w
er on terminal "7"? Replace s
w
itch
High temp limit s
w
itch tripped? Po
w
er on terminal
"8"?
Man
u
ally reset or replace
Lo
w
airflo
w
press
u
re s
w
itch contacts not made.
Po
w
er on terminal "8A"?
Check blo
w
er operation
Reconnect t
u
bes to press
u
re
s
w
itch
Clean press
u
re test t
u
bes
Check filters/d
u
ct
w
ork for restric-
tions
High airflo
w
press
u
re s
w
itch contacts not made.
Po
w
er on terminal "9"?
Check blo
w
er FLA and compare to
data plate.
Cabinet press
u
re too high check
system set
u
p and for restrictions
do
w
n stream of blo
w
er.
Optional: Mild
w
eather stat, dial set to lo
w
Set dial higher
Replace stat
Optional: High gas press
u
re s
w
itch
Man
u
al reset
Verify gas press
u
re
Optional: Lo
w
gas press
u
re s
w
itch
Man
u
al reset
Verify gas press
u
re
No po
w
er bet
w
een terminals 3 and L2 (ne
u
tral) or 6
and L2 (ne
u
tral) for RM7890A (5 and L2 (ne
u
tral) or
7 and L2 (ne
u
tral) for RM7897C) of the b
u
rner control
base
Verify
w
iring
Flame control defect
Replace
B
u
rner Locko
u
t
Fail
u
re to ignite pilot or main flame
Flame control fail
u
re
Reset the flame control mod
u
le at
the
u
nit and proceed to the next
step, obser
v
ing the
u
nit to indicate
at
w
hich step locko
u
t condition
occ
u
rs.
No PILOT flame
UV flame sensor indicating presence of flame before
ignition. Flame indicator light present? Is there 5VDC
on UV flame amplifier?
Separate spark
w
ire and UV scan-
ner
w
ires.
Replace UV flame sensor, UV
flame amplifier or b
u
rn control.
No spark
Check
w
iring from b
u
rner control to
ignition transformer.
Check high tension
w
ire to spark
pl
u
g.
Replace ignition transformer.
No gas
Open man
u
al gas sh
u
t off
v
al
v
es.
Check
w
iring from b
u
rner control to
pilot gas
v
al
v
e.
Verify inlet gas press
u
re.
Adj
u
st pilot gas press
u
re.
Replace pilot gas
v
al
v
e.
Check b
u
rner pilot opening for
obstr
u
ction.
Pilot flame does not stay lit
Improper pilot gas press
u
re
Adj
u
st pilot gas press
u
re.
UV flame scanner does not dedect flame, Is there
5VDC on UV flame amplifier?
Replace UV scanner
Replace UV flame amplifier
UV flame scanner dirty
Clean UV scanner
Содержание 2005
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 31: ...SECTION 7 ROOF CURB 21 of 147 FIGURE 12 Curb Mounting Air Handler Roof Curb Fastening Detail...
Страница 154: ...B SERIES INSTALLATION OPERATION AND SERVICE MANUAL 144 of 147...
Страница 158: ......
Страница 160: ......
Страница 161: ......
Страница 162: ......