5
If you set
P1.9
=drive selection to value 1=travel on the step 4, autotune the inverter. After autotuning,
go to step 8. Steps 6 and 7 are done only with compact brake motors.
AUTOTUNING
5.1 Ensure that parameters
P3.1
(Motor Nominal Voltage),
P3.2
(Motor Nominal Frequency),
P3.4
(Motor Nominal Current),
P3.5
(Motor Nominal Flux Current),
P3.6
(Motor Cos Phi) are equal to
the motor rating plate values If motor no-load current is not known, set
P3.5
(Motor Nominal Flux
Current) equal to zero. Auto-tuning then uses motor cos phi for calculations instead of no-load
current.
5.2 Set parameter
P3.7
(Autotuning) = 1. Auto-tuning will start right after the parameter change. RUN
indicator on the display turns on (and STOP indicator turns off). Autotuning will take about 5
seconds.
5.3 After auto-tuning, parameter
P3.7
(Autotuning) = 3, successfully done.
6
(only with compact brake motors)
Set motor control parameters.
•
P3.2
=Motor nominal frequency in percent of motor nominal voltage.
•
P4.1
=zero frequency voltage in percent of motor nominal voltage.
•
P4.2
=U/f mid voltage in percent of motor nominal voltage.
•
P4.3
=U/f mid frequency in Hz.
•
P4.4
=Rs voltage drop in percent of motor nominal voltage.
Table 8. Motor control parameters
Compact
brake
motors
CMX 022
ControlMaster ®NXT 006
Switch S4
Parameter
-1
-2
-3
-4
P3.2
P4.1 P4.2 P4.3 P4.4
MF06MA200
0
0
0
0
100/120
Hz
10%
14%
10%
0%
MF06MA100
1
0
1
0
80 Hz
9%
16%
8%
0%
MF06LA200
0
0
1
0
100/120
Hz
8%
12%
10%
0%
MF06LA100
1
0
0
1
80 Hz
6%
12%
8%
0%