7
(only with compact brake motors)
Set motor nominal current. You can set the parameter according to
this table or look the real value from the motor rating plate.
Table 9. Motor nominal current
CMX 022
Motor nominal
current limit
ControlMaster ®NXT
006
Switch S5
Parameter
-1
-2
P3.4
0
0
0…1,8A
1,8A
0
1
1,9…2,7A
2,7A
1
0
2,8…3,5A
3,5A
1
1
>3,5A
5,6A
8
At the ControlMaster ®NXT 006 frequency converter; Set
P3.8
=Start DC-Current. If you have multiple
motors, motor current values must be must be multiplied by the number of motors.
9
At the ControlMaster ®NXT 006 frequency converter; Set
P3.9
=current limit to 8.4A. This is the
maximum allowed temporary over current for one minute of time.
10
Set the control mode. The control mode settings in CMX 022 and the corresponding parameter value
for ControlMaster ®NXT 006 are given in table 6.
Table 10. Control mode
CMX 022
Control Method
ControlMaster ®NXT 006
Switch S6
Parameter
-1
-2
P6.1
0
0
MS2
2
1
0
EP2
1
11
Set travel limit operation settings. See chapter
New frequency controller installation (page 12)
, step 9,
how the control wiring was in the old inverter and how the new inverter wiring was done. In the new
inverter you need to set correct parameters in order to set travel limits to work. After setting the
parameters, test the limit functions.
Old CMX 022 inverter control
board connections
Original limit
settings
ControlMaster ®NXT 006 parameter
P6.2
P6.3
P6.4
X1:4 / DIA4
X1:5 / DIA 5
S11 , S21
3
0
1
X1:4 / DIA4
X1:5 / DIA 5
OL10
0
X1:3 / DIA3
S11, S21
3
R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319
27/34