94
Appendix II,
continued
Electrical Requirement Code of Magnetic Solenoid
SWITCH CODE DEFINITION 5 9 F, X, Y, 0
Use the chart above to select a suitable
electrical code for special solenoid (valve) types.
Note:
To find a switch code that works with your valve, you may need to use the trial and error method.
Example:
Activation Time =
40
ms. (milliseconds)
Arrows in chart show:
Holding Voltage =
2 .3
volts
Switch Code
=
59F450
If the solenoid opens but will not stay open, the holding voltage may be too low. Here, you would
change the fifth digit of the code.
Example:
Activation Time =
50 ms .
Holding Voltage =
5 .2 Volts
Switch Code
=
59F5A0
If the solenoids are still not operating properly after repeated attempts, contact your Rain Bird
®
Distributor to
guide you in adjusting this number for proper operation.