Quadnet Installation Instructions
21
Technical Data
Control Panel
Quadnet Control and Indicating Equipment
Dimensions
W x H x D
445mm x 445mm x 110mm
No. of zones
128 zones
Device labels
31 characters
LCD display
Graphic display
Field 1 (top)
Field 2
Field 3
Field 4 (bottom)
Control Panel Information Window
Active Information Window
Prompt Window
Network Information Window
LED Indication
Fire
Fault
Disablement
Test
Red - steady in general fire
pulsed (0.3s on, 0.5s off) from an MCP
yellow - intermittent (0.3s 0n, 2.1s off)
pulsed (0.3s 0n, 0.5s off)
yellow - continuous
yellow - pulsed (0.3s on, 0.5s off)
Audible Indication
2.5kHzBuzzer
continuous in fire
intermittent (0.3s on, 2.1s off) in fault
Keypad
4 way dedicated
17 way alphanumeric
Fire Alarm Controls
System Controls
Event log
1000 events
Inputs and Outputs
Relay Outputs x 4
Monitored Outputs
Monitored Inputs
volt free contacts SPCO
30vDC @ 2A max
volt free contacts SPCO
2 x 24v conventional monitored outputs
Fire, Fault, Signal, Technical Alarm
10k EOL, 200mA max per circuit
2 x resistance monitored inputs
3k3 EOL, 680R firing resistor
Power Supply
Working Range
19 - 32 V DC
Nominal Loop Operating Voltage
40v dc
Max loop current
500 mA
Response Times
First fire alarm event
New zone in alarm
Activate 32 alarm zones
+ve O/C detection
-ve O/C detection
spur O/C detection
Missing device
detection
1s
<10s
3s
1s
<10s
<35s
<35s
Environmental Data
IP Rating 30
Ambient Temp Range +5C to +40C
Power Supply Unit
Quadnet Power Supply Equipment
Dimensions
W x H x D
445mm x 445mm x 110mm
Power Supply
Standby batteries
Mains supply
Vmax
Vmin
Max cont output current
Ripple and noise
2 x 17Ah 12v sealed lead acid batteries
230v AC, +10%, -15%
29 –31.5V
20V
6.5A
<= 5% of Vmax