Quadnet Installation Instructions
20
Configuration Example
From your ‘As-Wired’ drawings device
addresses can be assigned, starting from
circuit end 1, with spurs being allocated at
the end.
From this the device attributes may be filled
out on the configuration sheets, as shown in
the following example.;
Control Panel No.:
01
Description:
West Wing
Loop No.:
1
Description:
Ground Floor
DEVICE
ADDRESS
SERIAL
NUMBER
DEVICE DESCRIPTION (24
CHARACTERS MAX)
ZONE
DEVICE
TYPE
SMOKE
MODE
HEAT
MODE
ALARM
CONF’N
1
212
Shop Floor: Main Entrance
1
MCP
-
-
-
2
30960
Staff Area: Rear Lobby
1
MPwS
SM2
HM2
-
3
213
Staff Area: Rear Exit
1
MCP
-
-
-
4
30962
Staff Area: Kitchen
1
MPwS
SM0
HM2
-
5
30963
Shop Floor: Rear
1
MP
SM2
HM2
-
6
30961
Shop Floor: Front
1
MPwS
SM2
HM2
-
7
30959
Boiler Room
2
MPwS
SM0
HM3
-
8
214
Boiler Room
2
MCP
-
-
-
These details may then be entered into the Quadnet OSP programming software in order to program the
operation of the system.