REGULATION INSTRUCTIONS
CONDENSING BOILOES WITH STORAGE - TG05A095.A0306
38
◄
PARAMETER N° 7 – CENTRAL HEATING PUMP
OVERRUN
7. Use
(
▲
) and (
▼
) buttons to modify the value of the
parameter:
00 = 0
99 = 99 x 5’’ = 450 ‘’ = 7.5’
Default value is set to 36 = 180’’ = 3’
8.
Press and release the service (
S
) button to confirm
your choice. Number 7 will appear on the display;
9.
If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
◄
PARAMETER N° 8 – D.H.W. PUMP OVERRUN
7. Use
(
▲
) and (
▼
) buttons to modify the value of the
parameter:
00 = 0
99 = 99 x 5’’ = 450 ‘’ = 7.5’
Default value is set to 18 = 90’’ = 1.5’
8.
Press and release the service (
S
) button to confirm
your choice. Number 8 will appear on the display;
9.
If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
◄
PARAMETER N° 9 – MINIMUM GAS RATE ON D.H.W.
7.
The value of the parameter must be equal to the one
shown into page 34 table.
Use
(
▲
) and (
▼
) buttons to set the parameter to the
default value of
20
both for Natural Gas & L.P.G..
8.
Press and release the service (
S
) button to confirm
your choice. Number 9 will appear on the display;
9.
If you have to modify some other parameter, follow
the 4 – 5 steps (p. 35), then go to the specific procedure
for that parameter, otherwise switch off and on the
appliance to register the modifications.
S
S
36
7
8
18
S
S
S
S
9
20