TELINK-SNMP1
Menu 3
Each input is associated to a tree for alarms settings. The tree for alarms settings
(or trap settings) can be found in section 110 of each subtree.
The adjustment of the class is not used in this release. For each analog
measurement can be set:
• The maximum value (MAX) is the fi xed point beyond which is sent a TRAP.
• The minimum value (MIN) is the fi xed point below which is sent a TRAP.
• The hysteresis value is a nominal value that the system adds (or subtracts) to
real value in order to exit from alarm condition.
In other words, it is helpful to avoid situations of continuous alarm, if readout
is very close to the set point alarm.