MQVL48 / MQVLB48
VENTED CHASE REQUIREMENTS
FIREPLACE CHASE MUST BE VENTED AT TOP AND BOTTOM
- Minimum
151
square inches free air opening at the top of the chase, and minimum
84
square
inches free air opening at the bottom of the chase.
Platform must have minimum
480
Square inches free air opening.
Chase Vent Openings
LARGER
than
the required minimums
ARE
allowed
and will reduce surface
temperatures.
HEAT CANNOT BE DISCHARGED INTO
THE WALLS, FLOOR, OR CEILING.
Heat
must exit through the required vented
chase opening near the ceiling.
ELECTRICAL WIRES IN CHASE MUST BE PROPERLY ATTACHED TO
INSIDE WALL OF CHASE. DO NOT RUN WIRES ABOVE APPLIANCE.
Please follow the current CSA C22.1 Canadian Electrical Code or the
National Electrical Code; ANSI/NFPA 70 when installed in the United States.
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.)
-Framing for Vented Chase with Grills-
MQVL48 / MQVLB48
-Framing for Vented Chase with Openings - No Grills-
84 Sq. In.
Air Option
Fireplace Support must be
open to allow air to flow
through fireplace.
Required
Minimum 151
Sq. In. Free
Air
Uses Kingsman
VL48EG
Grill
Or
Minimum 151 Sq.
In. Free Air
Equivalent
Required
Minimum 84 Sq.
In. Free Air
Fireplace Support must be
open to allow air to flow
through fireplace.
Ceiling
Ceiling
84 Sq. In.
Air Option
Uses Kingsman
VL48EG
Grill
Or
Minimum 151 Sq.
In. Free Air
Equivalent
Optional –
Secondary
Vent can be added
2” MAX
from
top of Chase
Required
Minimum 84
Sq. In. Free Air
Required
Minimum 84
Sq. In. Free Air
84 Sq. In.
Air Option
Required
Minimum 151
Sq. In. Free
Air
84 Sq. In.
Air Option
Required
Minimum 84
Sq. In. Free Air
*
This area must
be open -
MIN 480 Sq. In.
Min 151 Sq. In.
Can be in a
different
Pressure Zone
(Room / Area)
This area must
be open -
MIN 480 Sq. In.
*
Ceiling
2” MAX
from
top of Chase
Optional Adjustable Vented Platform (VL48AVP)
Optional –
Secondary
Vent can be added
Min 151 Sq. In.
Can be in a
different
Pressure Zone
(Room / Area)
11