Instruction book
2012 2039 28
86
9.
Technical Data
9.1 Electric information
Important
The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables at
nominal current below 5% of the nominal voltage (IEC 60204-1).
If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size.
Use the original cable entry. See section
To preserve the protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper
cable gland when connecting the supply cable to the compressor.
Local regulations remain applicable.
Currents are calculated with the full-service factor, but we suggest to add 10% due
to over- and under-voltage. Fuses are maximum allowed values for full-service factor
and 10% over- and under-voltage.
9.2 Reference conditions and limitations
Reference conditions
Air inlet pressure (absolute)
bar
1
Air inlet pressure (absolute)
psi
14.5
Air inlet temperature
˚C
20
Air inlet temperature
˚F
68
Relative humidity
%
0
Limits
Maximum working pressure
See section
Minimum working pressure
bar(e)
5.17
Minimum working pressure
psig
75
Maximum air inlet temperature
˚C
46
Maximum air inlet temperature
˚F
115
Minimum ambient temperature
˚C
0
Minimum ambient temperature
˚F
32
Содержание QSI 50
Страница 2: ......
Страница 16: ...Instruction book 2012 2039 28 16 Main components Main components...
Страница 61: ...Instruction book 2012 2039 28 61 Electric cubicle layout fixed speed Electric cubicle layout Variable speed...
Страница 88: ...Instruction book 2012 2039 28 88 Appendix 1 Product Analysis Report...
Страница 91: ...Instruction book 2012 2039 28 91...