background image

18

QUEST 100 

 

                                                   INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

QUESTCLIMATE.COM

(877) 420-1330

11.  Using capacitor or MFD setting on meter test between both capacitor terminals. Compare reading to  

 

 

capacitor spec on capacitor.

12.  If the above test pass but the compressor does not work, the compressor has an internal mechanical  

 

 

defect and must be replaced.

7.6B REPLACING A BURNT COMPRESSOR

The refrigerant and oil mixture in a compressor is chemically very stable under normal operating conditions. 
However, when an electrical short occurs in the compressor motor, the resulting high temperature arc causes 
a portion of the refrigerant oil mixture to break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise even small residues will attack replacement 
compressor motors and cause failures. 
The following procedure is effective only if the system is monitored after replacing the compressor to insure 
that the clean up was complete. 
1.  This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or 

open winding. 

2.   Remove and properly dispose of the system charge. DO NOT vent the refrigerant or allow it to contact your 

eyes or skin. 

3.  Remove the burned out compressor. Use rubber gloves if there is any possibility of contacting the oil or sludge. 
4.  To facilitate subsequent steps, determine the type of burn out that occurred. If the discharge line shows no 

evidence of sludge and the suction line is also clean or perhaps has some light carbon deposits, the burn out 
occurred while the compressor was not rotating. Contaminants are therefore largely confined to the compressor 
housing. A single installation of liquid and suction line filter/driers will probably clean up the system. 
If sludge is evident in the discharge line, it will likely be found in the suction line. This indicates the compressor 
burned out will running. Sludge and acid have been pumped throughout the system. Several changes of the 
liquid and suction filter/driers will probably be necessary to cleanse the system. 

5.  Correct the system fault that caused the burn out. Consult the factory for advice. 
6.   Install the replacement compressor with a new capacitor and an oversized liquid line filter. 

In a running burn out, install an oversized suction line filter/drier between the accumulator and compressor. 
Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to prevent the oil hole 
from becoming plugged. A standing burn out does not require a suction line filter/drier. 

7.  Evacuate the system with a good vacuum pump and accurate vacuum gauge. Leave the pump on the system 

for at least an hour. 

8.  Operate the system for a short period of time, monitoring the suction pressure to determine that the suction 

filter is not becoming plugged. Replace the suction filter/drier if pressure drop occurs. If a severe running burn 
out has occurred, several filter/driers may have to be replaced to remove all of the acid and moisture.  

NOTE: NEVER USE THE COMPRESSOR TO EVACUATE THE SYSTEM OR ANY PART OF IT.  

7.6C REPLACING A COMPRESSOR, NON BURN OUT

Remove the refrigerant from the system. Replace the compressor and liquid line filter/drier. Charge the 
system to 50 PSIG and check for leaks. Remove the charge and weigh in the refrigerant quantity listed on the 
nameplate. Operate the system to verify performance. 

Содержание 100

Страница 1: ...O M 87 7 420 1330 Patents thermastor com patents Serial Number Install Date Sold By 06 23 R E V A Compact Size Digital Controls Industry Leading Efficiency Superior MERV 13 Air Filtration Ducting Opt...

Страница 2: ...rd Air Filter 14 6 2 Impeller Fan Oiling 14 7 Service 15 7 1 Warranty 15 7 2 Technical Description 15 7 3 Troubleshooting 15 7 4 Refrigerant Charging 17 7 5 Impeller Fan Replacement 17 7 6 Compressor...

Страница 3: ...able DO NOT place the device directly on structural members Provide vibration isolation in order to minimize operational vibration and or noise A drain pan MUST be placed under the unit if installed a...

Страница 4: ...AGE 120 Volt 1 Phase 60 Hz CURRENT DRAW 5 0A RATED CURRENT DRAW 104 F 36 6 8A MINIMUM CIRCUIT AMPACITY MCA 8A MAXIMUM OVERCURRENT PROTECTION MOP 15A RECOMMENDED BREAKER SIZE 15A ENERGY FACTOR L KWH 3...

Страница 5: ...4 4 The unit should be suspended with a hang kit from the floor joists if there is any possibility of flooding A flooded unit is not covered by warranty Feet will be installed as a securing measure a...

Страница 6: ...year as this could diminish the water removal capability of the dehumidifier If the Check Damper is not used it is important to have the HVAC system fan ON when the dehumidifier is ON to prevent backf...

Страница 7: ...local codes prior to installing C DEDICATED QUEST RETURN TO HVAC RETURN Create a separate return for the Quest 100 Dehumidifier in a central area of the building Installing the supply air from the Qu...

Страница 8: ...e dehumidifier Install a 6 insulated duct from outside teeing into the 8 return duct of the Quest 100 Dehumidifier to provide outdoor air ventilation optional An 8 diameter duct is recommended for bra...

Страница 9: ...ore Be sure the extension is at a downward slope to the drain B An optional condensate pump kit may be installed if lift is required to remove condensate To order contact your local dealer or visit ou...

Страница 10: ...ERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330 4 4 HANGING DIAGRAM QUEST 100 4036668 Hang Bracket PN 4036668 Bottom view of dehumidifier and two brackets not included NOTE LEVELING...

Страница 11: ...area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any further information An optional remote de...

Страница 12: ...over the snowflake will light up when defrost is occurring ice is detected on coils The fan will be on and the compressor will be off during defrost FILTER RESET Filter reset button will light up afte...

Страница 13: ...ated when an external control is used to control RH When Terminal Control is active the internal RH sensor is disabled Pressing the Fan button alternates the unit between 3 fan speeds Hi gh Increased...

Страница 14: ...t Indicates when dehumidifier is in an alarm state NOTE Alarm terminals are used to interface with a remote alarm or building automation system The terminals switch when the unit has a malfunction and...

Страница 15: ...l where it absorbs heat from the incoming air and evaporates The evaporator operates in a flooded condition which means that all the evaporator tubes contain liquid refrigerant during normal operation...

Страница 16: ...ntrol or power board Fan is not running Dehumidification or fan is being called for 7 Loose connection in fan circuit 8 Obstruction prevents fan impeller rotation 9 Defective fan 10 Bad control or pow...

Страница 17: ...trical components 2 Plug in the unit and turn the humidity control to ON Check for volts from compressor black wires on compressor relay to white wire on compressor capacitor using an AC voltmeter 2 1...

Страница 18: ...r was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line filter driers will probably clean up the system If sludge is e...

Страница 19: ...ator it will sense the frost build up and automatically defrost the evaporator The Quest 100 Dehumidifier may not appear to be operating correctly during the defrost sequence but once the defrost sequ...

Страница 20: ...service people should service this unit TOOLS REQUIRED T25 Torx Driver 11 32 Driver Following all local and national electrical codes and standards route electrical service to the location that the de...

Страница 21: ...ound stud and use 11 32 driver to secure nut to stud Connect WHITE wire from LINE N terminal Connect BLACK wire from LINE L terminal Remove cord retention bracket Remove bushing from 7 8 hole 9 Replac...

Страница 22: ...6 TEMPERATURE TOO HIGH Error code E6 compressor off fan off Temperature too high Broken sensor Yes 7 TEMPERATURE TOO LOW Error code E7 compressor off fan off Temperature too low Broken sensor Yes 8 C...

Страница 23: ...use abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable c...

Страница 24: ...1 Comm Cable 7 4039294 Condenser 8 4039814 Compressor 9 4039815 Overload not pictured Item Part No Description 10 4041909 Display Assembly 11 4042005 Filter 12 4042066 01 Impeller 13 4042119 01 Base D...

Страница 25: ...25 QUEST 100 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330 3 7 8 9 10 1 4 5 11 14 13 12 16 17 2...

Страница 26: ...QUESTCLIMATE COM 877 420 1330...

Отзывы: