E. HVAC RETURN TO HVAC SUPPLY
F. NO EXISTING DUCTWORK INSTALLATION
When installing the Quest 100 Dehumidifier in a structure that does not have a forced-air HVAC system,
a single return for the dehumidifier should be installed in a central location. The supply air should be ducted back
into the space you want to dry. Proper air distribution is important for optimal performance of the dehumidifier.
Install a 6” insulated duct from outside, teeing into the 8” return duct of the Quest 100 Dehumidifier
to provide outdoor air ventilation (optional).
An 8” diameter duct is recommended for branches to larger areas.
Check Damper should be in place
between the Return and Supply
connections of the dehumidifier.
If the Check Damper is not in place,
the HVAC fan must be ON when
the dehumidifier is in operation.
Anything greater than 0.4” of static
requires HI fan setting. Anything greater
than 0.7” of static requires HI override
(99). Anything greater than 0.9” is not
recommended.