background image

 

18 

 

10.Servicing and maintenance. 
 

10.1. Servicing and maintenance must only be carried out by a competent unvented hot water 
installer or by Quantum Heating Limited authorised personnel. 
 
10.2. Before any work whatsoever is carried out on the installation, it MUST first be isolated 
from the mains electricity supply. 
 
10.3. 

WARNING

: both the primary and secondary systems will contain very hot water that will 

scald, therefore care should be taken when opening any joints, seals or valves. 
 
10.4. Only use spare parts authorised by Quantum Heating Limited. The use of unscheduled 
spare parts will invalidate the warranty. 
 
10.5. Drain the cylinder – When draining the cylinder, always switch off the boiler and the 
immersion heater first. Turn off the water supply at the stopcock (see Fig 5). Connect a hose pipe 
to the drain cock (see Fig 5) and route it to a convenient gulley. Open the drain cock and all hot 
taps that are served by the cylinder. The cylinder may take several minutes to empty completely. 

 

10.6. In hard water areas it may be necessary from time to time to remove and de-scale the 
immersion heater element. Replace the gasket each time it is removed.  
 
10.7. Remove the cartridge from the pressure reducing valve (PRV). Check the strainer and if 
necessary remove any debris from in front of it. Replace the cartridge. 
 
10.8 .Check the charge pressure in the expansion vessel and top up as necessary. The charge 
pressure should be 

3.0 bar

.  

 
10.9. Whilst the hose pipe is connected, the drain cock open and with the immersion heater 
removed, the cylinder may be flushed out to remove any debris, sand or lime scale particles that 
may have collected in the bottom by using a further hose pipe connected to the cold water main.  

 

10.10. Close the drain cock, disconnect the hose, refit the immersion heater and close all hot 
water taps before reopening the stopcock. Allow the cylinder time to fill whilst checking for any 
leaks. Release any air from the system by opening each hot water tap individually, starting with 
the one furthest from the cylinder. 
 
10.11. Manually lift the expansion relief and temperature and pressure relief valve one at a time, 
every 12 months (more frequently in hard water areas) to prevent debris from building up behind 
the valve seat. Whilst carrying out this operation, check that the discharge to waste is 
unobstructed. Check that each valve seals correctly when released. As the valves are pre-
calibrated, they require no further maintenance. 
 
10.12. Finally switch on the mains electricity supply to the immersion heater and the boiler. As 
the system heats up, check again for any leaks and rectify as necessary. 
 
 
 
 
 
 
 

Содержание Hot Spring

Страница 1: ...Storage Capacities 90 125 150 170 200 250 and 300 Litres Hot Spring Installation User and Service Manual Domestic Hot Water Cylinder...

Страница 2: ...12 User instructions 20 13 Warranty 20 1 Introduction The Quantum Hot Spring is a high quality stainless steel domestic hot water cylinder suitable for use on unvented or open vented hot water systems...

Страница 3: ...3 Performance Hot water generation time in minutes from 26 36 37 36 33 35 40 15 to 65 degrees C for Indirect cylinder Hot water generation time in minutes from 52 72 86 98 108 144 202 15 to 65 degrees...

Страница 4: ...e is 12 bar 4 4 Taps and fittings All taps and fittings incorporated in the unvented system should have a rated operating pressure of 7 bar or above 4 5 Location The unit is designed to be floor stand...

Страница 5: ...5 Pipework connections Fig 1 KEY ITEM DESCRIPTION A TEMPERAURE AND PRESSURE RELIEF VALVE B HOT WATER C HEATING WATER RETURN D THERMOSTAT POCKET E COLD WATER F IMMERSION HEATER G HEATING WATER FLOW...

Страница 6: ...er demand before switching over on to central heating duty If an existing system is a flow share arrangement such as a Honeywell S or Y plan type system see Figs 3 and 4 they will also provide satisfa...

Страница 7: ...7 W Plan wiring layout and system schematic...

Страница 8: ...8 Fig 2 Y Plan wiring layout and system schematic...

Страница 9: ...9 Fig 3 S Plan wiring layout and system schematic Fig 4...

Страница 10: ...torage volumes up to and including 200 litres For cylinders of 250 and 300 litres capacity a separate 24 litre expansion vessel is supplied which MUST be connected into the cold water supply side betw...

Страница 11: ...VALVE SET 6 BAR 6 DISCHARGE PIPE 22mm DIA SEE SECTION 7 7 DRAIN COCK 8 IMMERSION HEATER 230v 3 Kw 50 Hz 9 COLD WATER INLET CONNECTION 22mm DIA 10 PRIMARY FLOW CONNECTION 22mm DIA 11 CONTROL THERMOSTAT...

Страница 12: ...Downward discharge at low level i e up to 100 mm above external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children play or otherwise come into co...

Страница 13: ...13 Typical discharge pipe arrangement Fig 6...

Страница 14: ...Worked example The example below is for a diameter temperature relief valve with a discharge pipe D2 having 4 No elbows and a length of 7 m from the tundish to the point of discharge From Maximum res...

Страница 15: ...mit trip is factory set at 85 C The immersion heater conforms with EEC Directive 76 889 for radio interference and complies with BS 800 1977 WARNING Never fit an immersion heater without a thermal cut...

Страница 16: ...ontact separation of at least 3 mm using 1 5mm sq flexible cable 85 deg C rubber insulated HOFR sheathed to comply with BS 6141 table 8 and must be fully earthed d The BEAB approval certification on t...

Страница 17: ...the valve seating and to prove the correct function of the discharge arrangement 9 4 Check all joints for leaks rectify as necessary 9 5 Check that the control and high limit settings for the indirect...

Страница 18: ...e PRV Check the strainer and if necessary remove any debris from in front of it Replace the cartridge 10 8 Check the charge pressure in the expansion vessel and top up as necessary The charge pressure...

Страница 19: ...ult your boiler manufacturers instructions 3 High limit thermostat has 3 Check and re set tripped 4 Motorised valve malfunction 4 Check wiring and or plumbing connections to motorised valve Intermitte...

Страница 20: ...ols supplied with the cylinder for a period of 2 years from the date of purchase provided that they have been installed for their intended use by a competent person and have not been modified in any w...

Отзывы: