7. Discharge arrangement. 
 

Tundishes must be installed in a position so that they are clearly visible by the user. In addition, 
the discharge pipe from the Tundish should terminate in a safe place where there is no risk to 
persons in the vicinity of the discharge, be of metal and: 
 
(a) Be at least one pipe size larger than the normal outlet size of the safety device unless its total 
equipment hydraulic resistance exceeds that of a straight pipe 9 m long, i.e. discharge pipes 
between 9 m and 18 m equivalent resistance length should be at least two sizes larger then the 
normal outlet size of the safety device, between 18 m and 27 m at least three sizes larger and so 
on. Bends must be taken into account in calculating the flow resistance. Refer to the diagram, 
tables and worked example detailed in Fig 6. 

 

(b) Have a vertical section of pipe at least 300 mm long below the Tundish before any elbows or 
bends in the Pipework. 
 
(c) Be installed with a continuous fall 
 
(d) Have discharges visible at both Tundish and the final point of discharge, but where this is not 
possible or practically difficult, examples of acceptable discharge arrangements are:  

-

 

Ideally below a fixed grating and above the water seal in a trapped gully 

-

 

Downward discharge at low level, i.e. up to 100 mm above external surfaces such as 
car parks, hard standings, grassed areas, etc. are acceptable providing that where 
children play or otherwise come into contact with discharges, a wire cage or similar 
guard is positioned to prevent contact whilst maintaining visibility. 

-

 

Discharge at high level, e.g. into a metal hopper and metal down pipe with the end of 
the discharge pipe clearly visible (Tundish visible or not) or onto a roof capable of 
withstanding high temperature discharges of water and 3 m from any plastic guttering 
system that would collect such discharges (Tundish visible). 

-

 

Where a single pipe serves a number of discharges such as in blocks of flats, the 
number served should be limited to not more than six systems so that any installation 
discharging can be traced reasonably easily. The single common discharge pipe 
should be at least one pipe size larger than the largest individual discharge pipe to be 
connected. If unvented hot water stored systems are installed where discharges from 
safety devices may not be apparent i.e. in dwellings occupied by blind, or disabled 
people, consideration should be given to the installation of an electrically operated 
device to warn when discharge takes place. 

 

Warning Notice – 

The discharge will consist of scalding water and steam. Asphalt, roofing felt 

and non-metallic rainwater goods may be damaged by such discharges. 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Hot Spring

Страница 1: ...Storage Capacities 90 125 150 170 200 250 and 300 Litres Hot Spring Installation User and Service Manual Domestic Hot Water Cylinder...

Страница 2: ...12 User instructions 20 13 Warranty 20 1 Introduction The Quantum Hot Spring is a high quality stainless steel domestic hot water cylinder suitable for use on unvented or open vented hot water systems...

Страница 3: ...3 Performance Hot water generation time in minutes from 26 36 37 36 33 35 40 15 to 65 degrees C for Indirect cylinder Hot water generation time in minutes from 52 72 86 98 108 144 202 15 to 65 degrees...

Страница 4: ...e is 12 bar 4 4 Taps and fittings All taps and fittings incorporated in the unvented system should have a rated operating pressure of 7 bar or above 4 5 Location The unit is designed to be floor stand...

Страница 5: ...5 Pipework connections Fig 1 KEY ITEM DESCRIPTION A TEMPERAURE AND PRESSURE RELIEF VALVE B HOT WATER C HEATING WATER RETURN D THERMOSTAT POCKET E COLD WATER F IMMERSION HEATER G HEATING WATER FLOW...

Страница 6: ...er demand before switching over on to central heating duty If an existing system is a flow share arrangement such as a Honeywell S or Y plan type system see Figs 3 and 4 they will also provide satisfa...

Страница 7: ...7 W Plan wiring layout and system schematic...

Страница 8: ...8 Fig 2 Y Plan wiring layout and system schematic...

Страница 9: ...9 Fig 3 S Plan wiring layout and system schematic Fig 4...

Страница 10: ...torage volumes up to and including 200 litres For cylinders of 250 and 300 litres capacity a separate 24 litre expansion vessel is supplied which MUST be connected into the cold water supply side betw...

Страница 11: ...VALVE SET 6 BAR 6 DISCHARGE PIPE 22mm DIA SEE SECTION 7 7 DRAIN COCK 8 IMMERSION HEATER 230v 3 Kw 50 Hz 9 COLD WATER INLET CONNECTION 22mm DIA 10 PRIMARY FLOW CONNECTION 22mm DIA 11 CONTROL THERMOSTAT...

Страница 12: ...Downward discharge at low level i e up to 100 mm above external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children play or otherwise come into co...

Страница 13: ...13 Typical discharge pipe arrangement Fig 6...

Страница 14: ...Worked example The example below is for a diameter temperature relief valve with a discharge pipe D2 having 4 No elbows and a length of 7 m from the tundish to the point of discharge From Maximum res...

Страница 15: ...mit trip is factory set at 85 C The immersion heater conforms with EEC Directive 76 889 for radio interference and complies with BS 800 1977 WARNING Never fit an immersion heater without a thermal cut...

Страница 16: ...ontact separation of at least 3 mm using 1 5mm sq flexible cable 85 deg C rubber insulated HOFR sheathed to comply with BS 6141 table 8 and must be fully earthed d The BEAB approval certification on t...

Страница 17: ...the valve seating and to prove the correct function of the discharge arrangement 9 4 Check all joints for leaks rectify as necessary 9 5 Check that the control and high limit settings for the indirect...

Страница 18: ...e PRV Check the strainer and if necessary remove any debris from in front of it Replace the cartridge 10 8 Check the charge pressure in the expansion vessel and top up as necessary The charge pressure...

Страница 19: ...ult your boiler manufacturers instructions 3 High limit thermostat has 3 Check and re set tripped 4 Motorised valve malfunction 4 Check wiring and or plumbing connections to motorised valve Intermitte...

Страница 20: ...ols supplied with the cylinder for a period of 2 years from the date of purchase provided that they have been installed for their intended use by a competent person and have not been modified in any w...

Отзывы: