ActiveScale™ X100 Site Requirements Guide
24
Output Connector Ratings
Dimensions and weights
2.3.5.5 1-Phase 230V, 32A, Europe, Global
Input Power Configuration
Input Current/Power
Input Connector and Wiring
Short Term Peak (per branch)
<=16A
C13 Steady State Current
12A
C13 Short Term Peak Current
15A
C19 Steady State Current
16A
C19 Short Term Peak Current
20A
Width
2.2 in. / 55 mm
Height
69 in. / 1753 mm
Depth
2.25 in / 57 mm
Weight
18 lbs. / 8.2 kg
Number PDUs required by system including redundancy
4
Input Configuration
1-Phase
Nominal Input Voltage (line-to-neutral)
230VAC
Input Voltage Operating Range
220VAC-240VAC
Nominal Frequency
50Hz
Input Current, Steady State Available
32A, Europe, International
Input Current, Peak Available
32A
Input Power Available
7.3kVA at 230VAC, 32Amp
Input Wire Connections
2P+PE (2-Poles plus Protective Earth), 3-wire
Input Plug Compliant To
IEC 60309-1, IEC-60309-2
Input Plug Color Code
Blue (rated operating voltage of 200V to 250V, L-N)
Input Plug Ground Socket Position
6 Hour Position, Mates with Female in 6 Hour Position
Input Cord Wire Gauge
10 AWG