ActiveScale™ X100 Site Requirements Guide

14

2.1  Airflow considerations

Ensure that both the front and rear of the ActiveScale X100 stay clear of any materials that may block or 

disrupt the airflow in any way. Disrupting the airflow can cause the system to overheat which may affect 

performance or cause damage to the system.
The following rack airflow principles should be considered for best results:

• Controlled air conditioners that are functional and can sufficiently maintain specified system 

operating temperatures should be located in the facility where the system will be installed.

• The airflow in and out of the equipment must not be restricted.

2.2  Rack requirements

Note: 

Component tolerances in the rack can be very tight. Consequently, when 

measuring rack dimensions, measure to the millimeter or 1/32 of an inch.

The following is considered best practice when choosing a rack mounting solution for the ActiveScale 

X100:

System Dimension 

- select a 19" rack mounting solution that has inner dimensions of at least a height 

of 2100mm and a depth of 1200mm.

System Weight

 - consider whether the rack mounting solution selected can maintain the static loads 

required for a base system, dynamic loads if the system will be moved from its installation location, 

and the additional Storage Sleds that might be added later if the system is scaled up.

Cable Management 

- the system is designed so that most of the cables are wired at the back of the 

system. The exception is the Storage Enclosure Basic where the power and SAS cables cables connect 

in the front. Be sure that the system cabling can be routed safely and efficiently through the identified 

routes.

Grounding 

- ensure that the electrical components used to power the system can be grounded safely 

and that the rack itself can also be grounded safely.

Use the following table to make determinations about your rack mounting solution.

Table 2

-

1. Relevant System Specs for Rack Requirements

Specification

Value

Storage Enclosure Basic

W:

482.6mm (19in) x 

L:

1000mm (39.37in) x 

H:

177.8mm (7in)

Storage Node Dimensions

W:

448mm (17.64in) x 

L:

741mm (29.2in) x 

H:

43mm (1.7in)

System Node Dimensions

W:

448mm (17.64in) x

 L:

741 mm (29.2 in) x 

H:

43mm (1.7in)

System Interconnect Dimensions

W:

438mm (17.2in) 

L:

431mm (17in) 

H:

44mm (1.73in)

Management Interconnect Dimensions

W:

209mm (8.23in) x 

L:

250mm (9.84in) x 

H:

41.25mm (1.652in)

With mounting brackets, the width of the Management Interconnect 

extends completely between the vertical rails.

System Weight

Base Configuration - 

998 kg / 2200 lbs.

Scale-Up Kit - 

191 kg / 421 lbs.

Содержание ActiveScale X100

Страница 1: ...ActiveScale X100 Site Requirements Guide 6 68842 04 Rev A with ActiveScale OS 6 1 0 software...

Страница 2: ...uantum Corporation and its affiliates in the United States and or other countries All other trademarks are the property of their respective owners Quantum specifications are subject to change TRADEMAR...

Страница 3: ...Miscellaneous requirements 18 2 3 5 Example configurations 19 2 3 5 1 3 Phase Delta 208V 24A NA Japan Input Power Configuration 19 2 3 5 2 3 Phase Delta 208V 48A NA Input Power Configuration 21 2 3 5...

Страница 4: ...ActiveScale X100 Site Requirements Guide 4...

Страница 5: ...e 2 1 Relevant System Specs for Rack Requirements 14 Table 2 2 System Power Requirements 15 Table 2 3 Component Power Measurements 15 Table 2 4 Recommended startup order 19 Table 2 5 Contents of Activ...

Страница 6: ...ActiveScale X100 Site Requirements Guide List of tables 6...

Страница 7: ...ActiveScale X100 Site Requirements Guide List of figures 7 List of figures Figure 2 1 Minimum Servicing Space Required 28...

Страница 8: ...ActiveScale X100 Site Requirements Guide List of figures 8...

Страница 9: ...pter defines the scope of this document and provides a brief overview of the system site requirements It also lists the regulatory compliance information relevant to the product Topics Scope on page 1...

Страница 10: ...with data growth and deliver on your business objectives The minimum configuration is equipped with one sled column in all six Storage Enclosure Basics and provides either 0 84 PB of data storage capa...

Страница 11: ...3 configuration typical max 4 45 5 34 kW Base 4 configuration typical max 5 1 6 02 kW Base 5 configuration typical max 5 75 6 7 kW Full Base 6 configuration typical max 6 4 7 4 kW System Expansion Nod...

Страница 12: ...column of populated sleds 19 59 22 91 KBTU h Full configuration base 6 seven columns of populated sleds 21 83 25 25 KBTU h System Expansion Node kit 1 0 665 to 0 785 KBTU hour Weight Minimum system w...

Страница 13: ...t that a user must address in order to support the installation and operation of the system Topics Airflow considerations on page 14 Rack requirements on page 14 PDU requirements for rackless systems...

Страница 14: ...ed for a base system dynamic loads if the system will be moved from its installation location and the additional Storage Sleds that might be added later if the system is scaled up Cable Management the...

Страница 15: ...onfigurations that will not provide the required amount of power in a single connection For example there could be a lower power single phase PDU where one PDU cannot provide enough power for the Acti...

Страница 16: ...configuration Locking Locking connector preferred Connector Locking Spec 5lbs force retention Protection Device Manually resettable circuit breaker Protection Compliance UL489 Protection Temperature C...

Страница 17: ...input power configuration System Mounting Requirements Can be mounted in the rear of the rack and be contained fully within the outer dimensions of the rack except for the input power cord Neither th...

Страница 18: ...is drawn that is sometimes several times its normal full load current This is called inrush current While inrush current might only last for microseconds it can still pose a risk to the system and ass...

Страница 19: ...ompatibility EMC agency of the country that the rack is installed in Environmental Operating temperature 5 55 C 2 3 5 Example configurations The following sections provide examples of PDU configuratio...

Страница 20: ...liant To NEMA L15 30P Input Plug Color Code N A Input Plug Ground Socket Position N A Input Cord Wire Gauge 10AWG or equivalent Nominal 208VAC Operating Range 200VAC 220VAC Number of Branches 3 Total...

Страница 21: ...vailable 60A Input Power Available 17 3KW Input Wire Connections 3P PE 3 Poles plus Protective Earth 4 wire Input Plug Compliant To IEC 60309 1 IEC 60309 2 Input Plug Color Code Blue rated operating v...

Страница 22: ...uency 50Hz Input Current Steady State Available 16A Europe International Input Current Peak Available 16A Input Power Available 11 0kVA at 230VAC 16Amp Input Wire Connections 4P PE 4 Poles plus Protec...

Страница 23: ...4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 208VAC Input Voltage Operating Range 200VAC 240VAC Nominal Frequency 60Hz Input Current Steady State Available 24A NA derated Input...

Страница 24: ...g Number PDUs required by system including redundancy 4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 230VAC Input Voltage Operating Range 220VAC 240VAC Nominal Frequency 50Hz Inpu...

Страница 25: ...talled on site Because of this it is important to be sure that enough space is available for the individuals that will build the system to work While installing system components there needs to be a m...

Страница 26: ...lbs Each Storage Enclosure Basic box Rail kit Chassis Sleds I O Module Power cables SAS cables Screws and fasteners 2 Pallet weight 250kg 550lbs Pallet Dimensions 965 x 1220 x 635mm 38 x 48 x 25in 2 x...

Страница 27: ...65lbs Each Storage Node box Rail kits Screws and fasteners Storage Node Power cables 3 x System Nodes Box weight 30kg 65lbs Each System Node box Rail kits Screws and fasteners Storage Node Power cable...

Страница 28: ...he system components will need to be moved through the facility until it reaches the data center or computer room where the system will be installed This section describes the considerations that the...

Страница 29: ...rther assistance contact the Quantum Contact Support Center Region Support Contact North America 1 800 284 5101 toll free 1 720 249 5700 EMEA 1 800 7826 8888 toll free 49 6131 324 185 Asia Pacific 800...

Отзывы: