ActiveScale™ X100 Site Requirements Guide

19

To prevent the potentially negative effects of excessive inrush current on the system, Quantum Corporation 

recommends selecting a PDU that can stagger the startup sequence of the system components.

Important: 

If a PDU that cannot stagger the startup sequence is used, ensure that 

the PDU is rated to support the inrush current created by a simultaneous startup.

Table 2

-

4. Recommended startup order

For an example of the exact programming sequence used by Quantum Corporation power supplies, refer to 

the cabling section of the 

ActiveScale X100 Support Guide

.

Safety

The PDU used shall comply with the safety standards of the country that rack is installed in.

Electromagnetic Compatibility

The PDU used shall comply with the Electromagnetic Compatibility (EMC) agency of the country that the 

rack is installed in.

Environmental

Operating temperature: 5 – 55° C

2.3.5  Example configurations

The following sections provide examples of PDU configurations.

2.3.5.1 3-Phase Delta, 208V, 24A, NA, Japan Input Power Configuration

Input Current/Power

Recommended 

startup order

Component

Delay

1

System Interconnects

3-5 seconds for each device

2

System Nodes

3-5 seconds for each device

3

Management Interconnect

3-5 seconds for each device 

4

Storage Enclosure Basics

1-2 minutes for each device

Note: 

The longer delay for Storage Nodes allows all the 

disks in the Storage Enclosure Basics to spin up 

completely.

5

Storage Nodes

3-5 seconds for each device

Number of PDUs required by system including redundancy 2
Input Configuration

3-Phase DELTA

Nominal Input Voltage (line-to-line)

208VAC

Input Voltage Operating Range

200VAC-220VAC

Nominal Frequency

60Hz

Input Current, Steady State Available

24A, NA derated

Input Current, Peak Available

30A

Содержание ActiveScale X100

Страница 1: ...ActiveScale X100 Site Requirements Guide 6 68842 04 Rev A with ActiveScale OS 6 1 0 software...

Страница 2: ...uantum Corporation and its affiliates in the United States and or other countries All other trademarks are the property of their respective owners Quantum specifications are subject to change TRADEMAR...

Страница 3: ...Miscellaneous requirements 18 2 3 5 Example configurations 19 2 3 5 1 3 Phase Delta 208V 24A NA Japan Input Power Configuration 19 2 3 5 2 3 Phase Delta 208V 48A NA Input Power Configuration 21 2 3 5...

Страница 4: ...ActiveScale X100 Site Requirements Guide 4...

Страница 5: ...e 2 1 Relevant System Specs for Rack Requirements 14 Table 2 2 System Power Requirements 15 Table 2 3 Component Power Measurements 15 Table 2 4 Recommended startup order 19 Table 2 5 Contents of Activ...

Страница 6: ...ActiveScale X100 Site Requirements Guide List of tables 6...

Страница 7: ...ActiveScale X100 Site Requirements Guide List of figures 7 List of figures Figure 2 1 Minimum Servicing Space Required 28...

Страница 8: ...ActiveScale X100 Site Requirements Guide List of figures 8...

Страница 9: ...pter defines the scope of this document and provides a brief overview of the system site requirements It also lists the regulatory compliance information relevant to the product Topics Scope on page 1...

Страница 10: ...with data growth and deliver on your business objectives The minimum configuration is equipped with one sled column in all six Storage Enclosure Basics and provides either 0 84 PB of data storage capa...

Страница 11: ...3 configuration typical max 4 45 5 34 kW Base 4 configuration typical max 5 1 6 02 kW Base 5 configuration typical max 5 75 6 7 kW Full Base 6 configuration typical max 6 4 7 4 kW System Expansion Nod...

Страница 12: ...column of populated sleds 19 59 22 91 KBTU h Full configuration base 6 seven columns of populated sleds 21 83 25 25 KBTU h System Expansion Node kit 1 0 665 to 0 785 KBTU hour Weight Minimum system w...

Страница 13: ...t that a user must address in order to support the installation and operation of the system Topics Airflow considerations on page 14 Rack requirements on page 14 PDU requirements for rackless systems...

Страница 14: ...ed for a base system dynamic loads if the system will be moved from its installation location and the additional Storage Sleds that might be added later if the system is scaled up Cable Management the...

Страница 15: ...onfigurations that will not provide the required amount of power in a single connection For example there could be a lower power single phase PDU where one PDU cannot provide enough power for the Acti...

Страница 16: ...configuration Locking Locking connector preferred Connector Locking Spec 5lbs force retention Protection Device Manually resettable circuit breaker Protection Compliance UL489 Protection Temperature C...

Страница 17: ...input power configuration System Mounting Requirements Can be mounted in the rear of the rack and be contained fully within the outer dimensions of the rack except for the input power cord Neither th...

Страница 18: ...is drawn that is sometimes several times its normal full load current This is called inrush current While inrush current might only last for microseconds it can still pose a risk to the system and ass...

Страница 19: ...ompatibility EMC agency of the country that the rack is installed in Environmental Operating temperature 5 55 C 2 3 5 Example configurations The following sections provide examples of PDU configuratio...

Страница 20: ...liant To NEMA L15 30P Input Plug Color Code N A Input Plug Ground Socket Position N A Input Cord Wire Gauge 10AWG or equivalent Nominal 208VAC Operating Range 200VAC 220VAC Number of Branches 3 Total...

Страница 21: ...vailable 60A Input Power Available 17 3KW Input Wire Connections 3P PE 3 Poles plus Protective Earth 4 wire Input Plug Compliant To IEC 60309 1 IEC 60309 2 Input Plug Color Code Blue rated operating v...

Страница 22: ...uency 50Hz Input Current Steady State Available 16A Europe International Input Current Peak Available 16A Input Power Available 11 0kVA at 230VAC 16Amp Input Wire Connections 4P PE 4 Poles plus Protec...

Страница 23: ...4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 208VAC Input Voltage Operating Range 200VAC 240VAC Nominal Frequency 60Hz Input Current Steady State Available 24A NA derated Input...

Страница 24: ...g Number PDUs required by system including redundancy 4 Input Configuration 1 Phase Nominal Input Voltage line to neutral 230VAC Input Voltage Operating Range 220VAC 240VAC Nominal Frequency 50Hz Inpu...

Страница 25: ...talled on site Because of this it is important to be sure that enough space is available for the individuals that will build the system to work While installing system components there needs to be a m...

Страница 26: ...lbs Each Storage Enclosure Basic box Rail kit Chassis Sleds I O Module Power cables SAS cables Screws and fasteners 2 Pallet weight 250kg 550lbs Pallet Dimensions 965 x 1220 x 635mm 38 x 48 x 25in 2 x...

Страница 27: ...65lbs Each Storage Node box Rail kits Screws and fasteners Storage Node Power cables 3 x System Nodes Box weight 30kg 65lbs Each System Node box Rail kits Screws and fasteners Storage Node Power cable...

Страница 28: ...he system components will need to be moved through the facility until it reaches the data center or computer room where the system will be installed This section describes the considerations that the...

Страница 29: ...rther assistance contact the Quantum Contact Support Center Region Support Contact North America 1 800 284 5101 toll free 1 720 249 5700 EMEA 1 800 7826 8888 toll free 49 6131 324 185 Asia Pacific 800...

Отзывы: