ActiveScale™ X100 Site Requirements Guide
23
Dimensions and weights
2.3.5.4 1-Phase 220V, 24A, NA
Input Power Configuration
Input Current/Power
Input Connector and Wiring
Output Voltage
Branch Circuit Characteristics
C19 Steady State Current
16A
C19 Short Term Peak Current
20A
Width
2.2 in. / 55 mm
Height
70.5 in. / 1791 mm
Depth
2.2 in / 55 mm
Weight
18 lbs. / 8.2 kg
Number PDUs required by system including redundancy
4
Input Configuration
1-Phase
Nominal Input Voltage (line-to-neutral)
208VAC
Input Voltage Operating Range
200VAC-240VAC
Nominal Frequency
60Hz
Input Current, Steady State Available
24A, NA derated
Input Current, Peak Available
30A
Input Power Available
5.0kVA at 208VAC, 24Amp
Input Wire Connections
2P+PE (2-Poles plus Protective Earth), 3-wire
Input Plug Compliant To
NEMA L6-30P
Input Plug Color Code
N/A
Input Plug Ground Socket Position
N/A
Input Cord Wire Gauge
10AWG or equivalent
Nominal
208VAC
Operating Range
200VAC-240VAC
Number of Branches
2
Total Available Steady State Current (per branch)
<=13.8A, balanced