SANTA FE FREESTANDING

D. Draft

Draft is the pressure difference needed to vent an 

appliance successfully. When an appliance is drafting 

successfully, all combustion byproducts are exiting the 

home through the chimney.

Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

•  Preventing negative pressure

•  Location of appliance and chimney

E. Chimney and Exhaust Connection

1.  Chimney & Connector

:  Use 3 or 4 inch (76-102mm)  

diameter type “L” or “PL” venting system.  It can be 

vented vertically or horizontally.

NOTE

: The appliance exhaust outlet is designed to 

accommodate 3 inch venting. Use of 4 inch venting 

requires the use of a 3-to-4 inch exhaust vent increaser 

in addition to any other  venting components needed, 

sold separately.

2.  Mobile Home: 

Approved for all Listed pellet vent.  If 

using the 3 inch (76mm) vertical Top Vent Adapter Kit 

or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, 

use Listed double wall flue connector.  A Quadra-Fire 

Outside Air Kit must be used with manufactured home 

installations.

3.  Residential: 

 The 3 inch (76mm) vertical Top Vent 

Adapter Kit and the 3 to 6 inch (76-152mm) Top Vent 

Offset Adapter are tested to use 24 gauge single wall 

flue connector or Listed double wall flue connector to 

Class A Listed metal chimneys, or masonry chimneys 

meeting International Residential Code standards for 

solid fuel appliances.

WARNING

USE ONLY RECOMMENDED VENTING 

COMPONENTS; OTHERWISE MAKESHIFT PARTS 

MAY RESULT IN PROPERTY DAMAGE, PERSONAL 

INJURY, OR DEATH. 

NOTICE: 

Hearth & Home Technologies assumes no 

responsibility for the improper performance of the 

chimney system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

4.  INSTALL VENT AT CLEARANCES SPECIFIED BY 

THE VENT MANUFACTURER.

5.  Secure exhaust venting system to the appliance with 

at least 3 screws.  Also secure all connector pipe joints 

with at least 3 screws through each joint.

6. 

DO NOT INSTALL A FLUE DAMPER IN THE 

EXHAUST VENTING SYSTEM OF THIS Appliance.

7. 

DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are 

not located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

•  Attic mounted duct work and air handler joints and 

seams taped or sealed

NOTE:

  All pipe must be welded seam pipe whenever 

possible.  Seal pipe joints with high temperature 

silicone (500°F [260°C] minimum rated only).

F.  Venting Termination Requirements

DO NOT

 terminate vent in any enclosed or semi-

enclosed area such as a carport, garage, attic, crawl 

space, under a sun deck or porch, narrow walkway or 

closely fenced area, or any location that can build up 

a concentration of fumes such as a stairwell, covered 

breezeway, etc.

CAUTION

1.  Termination must exhaust above air inlet elevation. 

 

2.  Distance from

 

doors and opening windows, or gravity 

or ventilation air inlets into building:

a. 

Not less than 48 inches (1.2m) below;

b. 

Not less than 48 inches (1.2m) horizontally from;

c.  Not less than 12 inches (305mm) above.

3. 

Distance from permanently closed windows;

a. 

Not less than 12 inches (305mm) below; 

horizontally from or above.

4.  Distance between

 

bottom of termination and grade 

should be 12 inches (305mm) minimum.  This is 

conditional upon plants in the area, and nature of grade 

surface.  The grade surface must be a non-combustible 

material (i.e., rock, dirt).  The grade surface must not 

be lawn.  Distance between bottom of termination and 

public walkway should be 7 feet (2.13m) minimum.

5.  Distance to combustible

 

materials must be 24 inches 

(610mm) minimum.  This includes adjacent buildings, 

fences, protruding parts of the structure, roof overhang, 

plants and shrubs, etc.

6.  Termination Cap Location (Home Electrical Service)

•  Side-to-side clearance is to be the same as 

minimum clearance to vinyl inside corners.

•  Clearance of a termination cap below electrical 

service shall be the same as minimum clearance to 

vinyl soffits.

•  Clearance of a termination cap above electrical 

service will be 12 inches (305mm) minimum.

•  Location of the vent termination must not obstruct 

or interfere with access to the electrical service.

Содержание SANTAFE-MBK

Страница 1: ...llation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified professionals WARNING If the information in th...

Страница 2: ...Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearances to Combustibles UL...

Страница 3: ...st federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual EPA Certification 940 14 EPA Certified Emissions 1 8 grams per hour LHV Test...

Страница 4: ...om size out air must be installed G California Prop65 WARNING This product and the fuels used to operate this product wood and the products of combustion of such fuels can expose you to chemicals incl...

Страница 5: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Страница 6: ...arefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Reciprocating Saw Channel Locks Hammer Phill...

Страница 7: ...appliance and given to the party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this...

Страница 8: ...m 14 5 8 371mm 28 3 4 730mm 9 7 8 251mm 12 3 4 324mm 3 3 4 95mm 6 7 8 175mm 2 1 2 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top Vent A...

Страница 9: ...fset Adapter 812 3570 18 1 4 464mm 21 533mm 16 3 4 427mm 28 3 4 730mm 26 7 8 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View with Top Vent Ada...

Страница 10: ...ance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter with Clean out 812 3570 3 to 6 Offset Adapter 811 0720 3 to...

Страница 11: ...ded area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under...

Страница 12: ...Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth 36 914 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installations a...

Страница 13: ...ces and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in...

Страница 14: ...demands for your house Vent Configurations When installing a pellet appliance with a horizontal vent configuration the frequency of power outages should be considered Power outages during operation wi...

Страница 15: ...A CHIMNEY FLUE SERVING ANOTHER APPLIANCE To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating season Ensure adequate...

Страница 16: ...s not intended to represent any specific fuel type Figure 16 2 3 in or 4 in 76mm or 102mm Diameter Pipe Equivalent Pipe Length In Feet ALTITUDE IN THOUSANDS OF FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 1...

Страница 17: ...installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall or p...

Страница 18: ...3 in 76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations a...

Страница 19: ...ce Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance wit...

Страница 20: ...tion on wall Use saw to cut opening in wall Cut a 2 1 2 to 3 inch 64 76mm opening on inside wall and a 3 to 3 1 2 inch 76 89mm opening on outside of house 2 Remove cover plate and then install the col...

Страница 21: ...he assembly is vertical Figure 21 2 4 Install the 4 mounting screws 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the top...

Страница 22: ...nder or in front of appliance CAUTION Figure 22 1 Figure 22 2 Figure 23 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the two pieces apart Figure 22 1 2 Use a drill...

Страница 23: ...firebox 4 Push the logs to the far left and far right against the sides of the firebox Figure 23 2 5 To clean the logs use a vacuum and a soft brush attachment or a paint brush Figure 23 2 Figure 23 1...

Страница 24: ...24 Part Number 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION Never draw outside combustion air from Wall floor or ceiling...

Страница 25: ...August 3 2018 7050 145L 25 SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Страница 26: ...26 7050 145L August 3 2018 SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Страница 27: ...utside Air Kit 412 7100 Pull Rod Handle PULLROD HNDL Smart Batt Il Battery Operated 841 0970 Smart Stat Il receiver Requires 110 VAC 841 0960 Thermostat Programmable PROG STAT Top Vent Adapter TPVNT 2...

Страница 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Отзывы: