SANTA FE FREESTANDING

EMBER PROTECTION:  

It is necessary to install a Type I 

floor protector.

Floor protector must be non-combustible material, 

extending beneath appliance with a minimum of 6 inches 

(152mm) in front of glass  and 6 inches (152mm) to both 

sides of the fuel loading door.  Open the door and measure 

6 inches  (152mm) from the side edge of the opening in the 

face of the appliance.*

See exception. 

27 in.

minimum

26-1/2 in. 

minimum

6 in

from the fuel door 

opening

6 in

USA

15 in

6 in

FUEL DOOR OPENING

152MM

FROM FUEL DOOR 

OPENING

152MM

686mm

minimum

673mm

 minimum

CANADA

Must extend 51mm 

beyond each side 

of pipe (shaded area) 

to the wall thimble.

152MM

FUEL DOOR OPENING

USA INSTALLATIONS

: A

 non-combustible floor protection 

is recommended extending beneath the flue pipe when 

installed with horizontal venting or under the Top Vent 

Adapter with vertical installation.

CANADA INSTALLATIONS

:  A non-c

ombustible floor 

protection 

extending beneath the flue pipe 

is 

required

 

with horizontal venting or under the Top Vent Adapter with 

vertical installation.

Figure 11.1

Figure 11.2

39-5/8 in.

22-3/4 in.

15 in.

32-1/4 in.

6 in.

from the fuel door 

opening

USA

1006mm

578mm

381mm

819mm

152mm

(front door opening)

CANADA

Must extend 51mm 

beyond each side 

of pipe (shaded area) 

to the wall thimble.

Figure 11.3

Figure 11.4

C. Hearth Pad Requirements (UL and ULC)

Fire Risk

Comply with all minimum clearances to 

combustibles as specified.

Failure to comply may cause house fire.

WARNING

Содержание SANTAFE-MBK

Страница 1: ...llation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends HHT Factory Trained or NFI certified professionals WARNING If the information in th...

Страница 2: ...Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearances to Combustibles UL...

Страница 3: ...st federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual EPA Certification 940 14 EPA Certified Emissions 1 8 grams per hour LHV Test...

Страница 4: ...om size out air must be installed G California Prop65 WARNING This product and the fuels used to operate this product wood and the products of combustion of such fuels can expose you to chemicals incl...

Страница 5: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Страница 6: ...arefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Reciprocating Saw Channel Locks Hammer Phill...

Страница 7: ...appliance and given to the party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this...

Страница 8: ...m 14 5 8 371mm 28 3 4 730mm 9 7 8 251mm 12 3 4 324mm 3 3 4 95mm 6 7 8 175mm 2 1 2 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top Vent A...

Страница 9: ...fset Adapter 812 3570 18 1 4 464mm 21 533mm 16 3 4 427mm 28 3 4 730mm 26 7 8 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View with Top Vent Ada...

Страница 10: ...ance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter with Clean out 812 3570 3 to 6 Offset Adapter 811 0720 3 to...

Страница 11: ...ded area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under...

Страница 12: ...Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth 36 914 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installations a...

Страница 13: ...ces and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in...

Страница 14: ...demands for your house Vent Configurations When installing a pellet appliance with a horizontal vent configuration the frequency of power outages should be considered Power outages during operation wi...

Страница 15: ...A CHIMNEY FLUE SERVING ANOTHER APPLIANCE To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating season Ensure adequate...

Страница 16: ...s not intended to represent any specific fuel type Figure 16 2 3 in or 4 in 76mm or 102mm Diameter Pipe Equivalent Pipe Length In Feet ALTITUDE IN THOUSANDS OF FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 1...

Страница 17: ...installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall or p...

Страница 18: ...3 in 76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations a...

Страница 19: ...ce Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance wit...

Страница 20: ...tion on wall Use saw to cut opening in wall Cut a 2 1 2 to 3 inch 64 76mm opening on inside wall and a 3 to 3 1 2 inch 76 89mm opening on outside of house 2 Remove cover plate and then install the col...

Страница 21: ...he assembly is vertical Figure 21 2 4 Install the 4 mounting screws 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the top...

Страница 22: ...nder or in front of appliance CAUTION Figure 22 1 Figure 22 2 Figure 23 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the two pieces apart Figure 22 1 2 Use a drill...

Страница 23: ...firebox 4 Push the logs to the far left and far right against the sides of the firebox Figure 23 2 5 To clean the logs use a vacuum and a soft brush attachment or a paint brush Figure 23 2 Figure 23 1...

Страница 24: ...24 Part Number 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION Never draw outside combustion air from Wall floor or ceiling...

Страница 25: ...August 3 2018 7050 145L 25 SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Страница 26: ...26 7050 145L August 3 2018 SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Страница 27: ...utside Air Kit 412 7100 Pull Rod Handle PULLROD HNDL Smart Batt Il Battery Operated 841 0970 Smart Stat Il receiver Requires 110 VAC 841 0960 Thermostat Programmable PROG STAT Top Vent Adapter TPVNT 2...

Страница 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Отзывы: