MT VERNON E2 INSERT-C
C.  Negative Pressure

WARNING

USE ONLY RECOMMENDED VENTING COMPONENTS; 

OTHERWISE MAKESHIFT PARTS MAY RESULT IN PROP

-

ERTY DAMAGE, PERSONAL INJURY, OR DEATH. 

Negative  pressure  results  from  the  imbalance  of  air  avail

-

able for the appliance to operate properly. It can be strongest 

in lower levels of the house.
Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods

•  Combustion  air  requirements  for  furnaces,  water 

appliances and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or air conditioning
•  Imbalances of the HVAC air handling system
•  Upper level air leaks such as: 

  -  Recessed lighting
  -  Attic hatch
  -  Duct leaks

To minimize the effects of negative air pressure:
•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for 

all

 combustion appliances 

and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid  installing  the  appliance  near  doors,  walkways  or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

•  Attic mounted duct work and air handler joints and seams 

taped or sealed

D.  Draft 

Draft is the pressure difference needed to vent an appli

-

ance successfully. When an appliance is drafting suc-

cessfully, all combustion byproducts are exiting the home 

through the chimney.

Install through the warm airspace enclosed by the build

-

ing envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

•  Preventing negative pressure

•  Location of appliance and chimney

NOTICE: 

Hearth & Home Technologies assumes no 

responsibility for the improper performance of the chimney 

system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

E.  Chimney and Exhaust Connection 

1.

 

Chimney & Connector

:  Use 3 or 4 inch (76-102mm)  diameter 

type “L” or “PL” venting system.  It can be vented vertically or 

horizontally.

2.

  Mobile Home: 

Approved for all Listed pellet vent.  If using the 3 

to 6 inch (76-152mm) Top Vent Offset Adapter, use Listed double 
wall flue connector.  A Quadra-Fire Outside Air Kit (OAK-3) must 
be used with manufactured home installations.

3.

  Residential: 

 The 3 inch (76mm) vertical Top Vent Adapter Kit and 

the 3 to 6 inch (76-152mm) Top Vent Offset Adapter are tested 
to use 24 gauge single wall flue connector or Listed double wall 
flue connector to Class A Listed metal chimneys, or masonry 

chimneys meeting International Residential Code standards for 
solid fuel appliances.

4.

  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 

VENT MANUFACTURER.

5

Vent Assembly to Insert Instructions:

These  instructions  are  for  connecting  the  vent  pipe  to  the 

vent assembly prior to installing the appliance in the fireplace. 

a. Unlatch the vent assembly for the exhaust blower and     

 

      attach  to  the  vent  pipe  end  using  high  temperature 

 

    silicone and at least three screws. 

b.  Slide  the  appliance  into  place  and  line  up  the  bent 

 

    assembly with the exhaust blower. 

c. Make sure the high-temperature gasket is in place. 

d. Latch the top vent assembly to the exhaust blower. 

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENT

-

ING SYSTEM OF THIS Appliance.

7.  DO  NOT  CONNECT THIS Appliance TO A  CHIMNEY  FLUE 

SERVING ANOTHER APPLIANCE.

8.  Disconnect the vent pipe from the appliance to allow removal 

of the fireplace insert for the purpose of inspecting the fireplace 
insert and the fireplace. 

NOTE:  All pipe must be welded seam pipe whenever possible.  

Seal pipe joints with high temperature silicone (500°F [260°C] 

minimum rated only).

WARNING

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 

fumes and soot.

NOTE

: The appliance exhaust outlet is designed to ac

-

commodate 3 inch venting. Use of 4 inch venting requires 

the use of a 3-to-4 inch exhaust vent increaser in addition 

to any other  venting components needed, sold separate

-

ly.

Содержание MTVI-E2-CSB-C

Страница 1: ...ot store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing...

Страница 2: ...Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearance To Combustibles US Canada 8 C Minimum Opening for Masonry Zero Clearance Fireplaces 9 D Hearth Extension 9 E Floo...

Страница 3: ...9 Amps Run 2 45 Amps E Mobile Home Approved This appliance is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided The stru...

Страница 4: ...of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney of...

Страница 5: ...on unless installing into an existing masonry fireplace B Tools And Supplies Needed C Inspect Appliance and Components Open the appliance and remove all the parts and articles packed inside the Compon...

Страница 6: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Страница 7: ...605mm 26 7 8 in 683mm 11 7 8 in 302mm 24 1 8 in 613mm 33 in 838mm 50 in 1270mm 34 1 2 in 876mm 45 in 1143mm 11 3 4 in 297mm 18 1 2 in 469mm Figure 7 2 Front View with Cast Panel Set 23 7 8 in 606mm 32...

Страница 8: ...or choice must be added to this dimension B Clearance To Combustibles US Canada Figure 8 1 Built in Appliance Rear Vent NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONL...

Страница 9: ...4 inches Minimum Opening Dimensions Inches Millimeters A Height 24 3 8 619 B Front Width Steel Panel Set 32 1 4 819 Front Width Cast Panel Set 32 1 4 819 C Back Width 24 1 8 613 D Depth Steel Panel Se...

Страница 10: ...250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Heath Home Technolog...

Страница 11: ...lace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and t...

Страница 12: ...lk paved driveway located on public property M 12 in Under an open veranda porch deck or balcony N See Note below Electric service above below or to the side location must not obstruct or interfere wi...

Страница 13: ...demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation...

Страница 14: ...nstruction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented vertically...

Страница 15: ...to the equivalent feet of pipe calculated previously and the altitude above sea level of this installation Figure 15 2 a Locate the calculated equivalent feet of pipe on the vertical left side of the...

Страница 16: ...side combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams...

Страница 17: ...Air Vertical Figure 17 1 NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insulation such as fiberglass mineral wool or ceramic Do not use high temperature caulking...

Страница 18: ...space such as an attic or garage Figure 18 1 Collar Wire Ties Trim Ring Termination Cap 3 inch Aluminum Flex Pipe not included Figure 18 2 OAK Exploded View Lower the leveling bolts if necessary to k...

Страница 19: ...cast trim header 2 cast trim footers left and right 1 fastener package Tools Needed Powered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim p...

Страница 20: ...crews provided Figure 20 3 Back of Top Surround Back of Side Surround Screws Figure 20 1 Shown with trim installed on panel set G Optional Log Set Placement Instructions 2 PIECE LOG SET INSTALLATION 1...

Страница 21: ...e located on an inside wall approximately 5 up from the floor W R Saturday and Sunday can be programmed individually by changing the format from 5 2 to 5 1 1 To change the format 1 Press and hold the...

Страница 22: ...ermostat should be located on an inside wall approximately 5 up from the floor PROGRAMMABLE THERMOSTAT PART WALL STAT P W R Saturday and Sunday can be programmed individually by changing the format fr...

Страница 23: ...es when burning on high A prop erly adjusted fire will burn cleaner and have higher efficiencies Please copy and paste the follow web address http www quadrafire com Owner Re sources Use and Care Vide...

Страница 24: ...4 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 24 1 CAUTION Never draw outsi...

Страница 25: ...January 4 2018 7082 150C 25 MT VERNON E2 INSERT C A Service and Maintenance Log Date of Service Performed By Description of Service 8 Reference Materials...

Страница 26: ...26 7082 150C January 4 2018 MT VERNON E2 INSERT C Date of Service Performed By Description of Service...

Страница 27: ...nly LOGS 60 AE B Y Outside Air Kit OAK 3 Top Vent Adapter TPVNT 4 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim SP MTVS GD Component Pack 7036 042...

Страница 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Отзывы: