![Quadra-Fire EXPLRMED-PBK Скачать руководство пользователя страница 8](http://html2.mh-extra.com/html/quadra-fire/explrmed-pbk/explrmed-pbk_installation-manual_3445250008.webp)
8
7061-197I
December 3, 2015
Explorer II Medium Wood Stove
B. Clearances to Combustibles
BACKWALL / SIDEWALL
A
B
C
D
F
CORNER INSTALLATION
E
C
ALCOVE TOP VIEW
G
A
ALCOVE SIDE VIEW
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specifi ed.
• Failure to comply may cause house fi re.
WARNING
A B C D
INSTALLATION: FULL VERTICAL OR ALCOVE
SINGLE WALL PIPE
DOUBLE WALL PIPE
Explorer II
9-3/8 (238) 5-3/8 (137) 20-1/4 (514) 6-1/2 (165) 4-1/2 (114) 14-3/4 (375) 55 (1397)
Explorer II
10-1/2 (267) 6-1/2 (165) 20-1/4 (514) 6-1/2 (165) 7 (178) 17-1/4 (438) 55 (1397)
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches & (Millimeters)
NOTE: A, C, and F Dimensions are to the center of the flue collar
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with UL103 HT
listed factory built Class A chimney or masonry chimney. Maximum depth of Alcove shall be no
more than 48 inches (1220mm) with a minimum height of 48 inches (1220mm) to top of unit and
the referenced clearances. Canada must comply with CAN/ULC-S269 M87 for the 650° factory
built chimney
E
F
G
* FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED
G
STOVE TO CEILING
CLEARANCE
*
12
(305)
20.25
(514)
50
(1270)
MANTEL
12” MAX
HORIZONTAL THROUGH WALL
TOP AND SIDE VIEW