14
7061-197I
December 3, 2015
Explorer II Medium Wood Stove
54-5/8 in.
1388mm
31-7/8 in
810mm
19-1/4 in.
489mm
45-1/2 in.
1156mm
16
(FRONT
DOOR OPENING)
35-5/8 in.
minimum
8 in.
35 1/4 in.
minimum
16 in. from glass
Fuel door opening
Figure 14.2
Figure 14.1
Figure 14.3
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1175mm
(46-1/4 in.)
minimum
1143mm (45 in.)
minimum
A. Hearth Protection Requirements
FLOOR PROTECTION:
Floor protector must be non-combus-
tible material, extending beneath heater and to the front, sides
and rear as indicated. The fl oor must be non-combustible or
otherwise adequately protected from radiant heat given off by
the unit and from sparks and falling embers. A layer of thin
brick or ceramic tile over a combustible fl oor is not suffi cient.
It is necessary to install a fl oor protector (Type I) of a minimum
of 3/8 inch (9.5mm) thick metal clad millboard or equivalent
a minimum of 16 inches (406mm) in front of glass and 8
inches (203mm) to both sides of the fuel loading door. Open
the door and measure 8 inches (203mm) from the side edge
of the opening in the face of the appliance. *
See exception.
In Canada,
similar fl oor protection must be provided 18 inches
(457mm) in front and 8 inches (203mm) from the sides and
rear of the stove.
Figure 14.2
*EXCEPTION:
Non-combustible floor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See
Figure 14.4
WARNING
Fire Risk.
Hearth pads must be installed exactly as specifi ed.
High temperatures or hot embers may ignite concealed
combustibles.
58-1/4 in.
1480mm
34-3/8 in.
873mm
19-1/4 in.
489mm
48 in.
1219mm
16
(FRONT
DOOR OPENING)
Figure 14.3
USA
CANADA
5
Appliance Set-Up
Corner hearth pad dimensions
with single wall pipe
Corner hearth pad dimensions
with double wall pipe