R
October 24, 2011
Page 27
Castile & Santa Fe CE Pellet Stove
7068-112B
We strongly recommend a minimum of
1.5m vertical, however above the eave is
preferred.
Both installations are approved for mobile home
installations. Must use 76mm to 102mm “L” or “PL”
Listed pellet venting or Listed double wall pipe and
Quadra-Fire Outside Air Kit in mobile homes. Single
wall pipe is approved for residential installations only.
Air Clearance to Pipe
:
This appliance was tested with standard 76mm
Listed pellet clearance pipe to combustibles.
Pellet pipe manufactures Listed reduce clearance
pipe may be use for reduce clearance from 76mm
air clearance to no less than 25mm air clearance to
combustibles for approved Listed pellet pipe.
Follow stove pipe manufactures listed air clearances
to combustibles and installation instructions for all
reduced air clearances installations.
The stove must be connected to a flue pipe
conforming to current standards UNI 7129-7131
9615.
D. Vertical into Existing Chimney
(SHOWN ON A SANTA FE)
C. Through The Wall & Vertical - External
(SHOWN ON A SANTA FE)
Firestop
Flashing
Rain Cap
152mm
Minimum
Non-combustible Hearth Pad
76mm
Minimum
Cleanout Cover
305mm
Minimum
Ceiling Support
152mm)Flue
Connector
Connector Adapter
76mm-152mm
Top Vent Kit
Non-combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support
Bracket
every 1.5m
610mm
Minimum
Rain Cap
Flashing
51mm minimum
152mm
Minimum
Figure 28.3
Figure 28.2
Firestop
Flashing
Rain Cap
152mm
Min.
Non-combustible Hearth Pad
76mm
Min.
305mm
Minimum
76mm-76mm)
Top Vent Kit
Clean-out Cover
on other side
B. Vertical - Interior - Typical Installation
(SHOWN ON A SANTA FE)
Figure 28.1
PREFERRED METHOD #1
PREFERRED METHOD #2