background image

 16 

 

 

 

 

                        7047-910 

 

 

 

          October 14, 2013

5100 I-ACC

Figure 16.1 

  

Optional 

Flex 

Adapter

Termination 

Cap

Appliance 

Cover Plate 

(discard)

Remove 4 bolts on Blower Housing 

(both sides)and Remove Housing

Remove 2 screws and Secure Outside 

Cover Plate to the back side of the Blower 

Housing (included in Component Pack)

A. Outside Air Kit Installation

Items Needed for Installation (not supplied)

  •  4  inch  flex  aluminum  pipe,  or  if  using  alternate  material, 

then it shall be made from durable, non-combustible, heat 

resistant material up to 350

o

F.  Cut the pipe to the required 

length for your installation. 

  • Phillips head screw driver 

  • 5/32 Allen Wrench 

  • Silicone sealant

A source of air (oxygen) is necessary in order for combustion 

to  take  place.    Whatever  combustion  air  is  consumed  by  the 

fire must be replaced.  Air is replaced via air leakage around 

windows and under doors. In homes that have tightly sealed 

doors and windows, an outside air source is needed. An optional 

Outside Air Kit is available. 

WARNING

Do not draw outside combustion air from:
•  Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

•  Close proximity to exhaust vents or 

chimneys

Fumes or odor may result

Fire Risk.
Asphyxiation Risk.

Asphyxiation Risk.

Outside air inlet must be located to prevent block-

age from:

•  Leaves, snow, ice or other debris

Block may cause combustion air starvation
Smoke spillage may set off alarms or irritate sensi-

tive individuals.

WARNING

Asphyxiation Risk.

Length of outside air supply duct shall NOT exceed 

the length of the vertical height of the exhaust flue.

• 

Fire will not burn properly

  Smoke spillage occurs when door is opened due 

to air starvation.

WARNING

Option One - Installation Instructions

The  outside  air  cover  comes  packaged  with  the  component 

pack.  It is necessary to remove the blower housing and block 

off the room air with the outside air cover.
1.  Remove the appliance cover plate on outer can and discard 

and reuse the 4 screws.

2.  Install  optional  flex  adapter  to  outer  can  with  the  same 

screws.  Do not use plastic wire ties that come with the kit 

as they will melt.  NOTE:  You may need to install the flex 

pipe into the firebox first depending on installation. Attach 

flex to adapter with at least 2 screws.

3.  Ensure existing access hole in fireplace is sufficient to feed 

the 4 inch flex.

4.  After sliding can into fireplace, feed flex into cut opening to 

obtain outside combustion air.

5.  Level outer can and install appliance.  See 

page 18.

6.  Remove 4 bolts from both sides of the blower housing and  

remove the housing.

7.  Remove 2 Phillips head screws from housing and save.
8.  Attach outside air cover to the back of the blower using the 

same 2 screws.

9.  Ensure all wires are properly attached and then re-install 

the blower housing to the appliance.

Option Two - Installation Instructions

1.  Remove the outside air cover plate on outer can and dis-

card and reuse the 4 screws

2.  Ensure existing access hole in fireplace will not be covered 

by the outer can. Existing outside air intake hole may be 

under at the rear or side of outer can.  Outside air may also 

enter down existing chimney chase in some situations.

3.  Repeat steps 5 through 9 above with one exception.  After 

installing the appliance in the outer can, seal the fireplace 

opening and trim package with insulation to prevent air leak-

age into the room.

Appliance Set-Up

Содержание 5100 ACC

Страница 1: ...pliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING Fire Risk For use with solid wood fuel only Other fuels may overfire and generate poisonous gases i e carbon monoxide Installation and service of this appliance should be pe...

Страница 2: ...pplies Needed 5 E Inspect Appliance and Components 5 F Install Checklist 6 3 Dimensions and Clearances A Appliance Dimensions 7 B Clearances to Combustibles 8 C Locating Your Stove Chimney 9 D Chimney Termination Requirements 9 E 2 10 3 Rule 10 4 Chimney Systems A Venting Systems 11 B Inspections 11 C Larger Chimneys 11 D Masonry Chimney 11 E Metal Heat Circulating Masonry 13 F Prefabricated Metal...

Страница 3: ...tered trademark of Hearth Home Technologies Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Operating appliance without fully assembling all components Operating appliance without legs attached if supplied with unit Do ...

Страница 4: ...nd national codes and regulations Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits CAUTION WARNING DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVICING ANOTHER APPLIANCE DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM May allow flue gases to enter the house Asphyxiation Risk Installation and use ...

Страница 5: ... air handler joints and seams taped or sealed Basement installations should be avoided D Tools And Supplies Needed Before beginning the installation be sure the following tools and building supplies are available Reciprocating saw Framing material Pliers High temp caulking material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety gl...

Страница 6: ...height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 7 Combustible materials not installed in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hearth extension installed per manual requirements Applianc...

Страница 7: ...6 11 16 in 678mm 9 1 8 in 232mm 21 3 16 in 538mm 20 3 4 in 528mm 12 1 16 in 306mm 30 5 8 in 762mm Surround Sizes A B Standard 43 in 1092mm 31 in 787mm Large 53 in 1346mm 34 in 864mm 20 1 8 to 23 1 2 in 512 to 896mm 15 34 to 19 in 399 to 483mm 7 7 8 in 200mm Figure 7 4 Side View With Optional Offset Adapter 3 Dimensions and Clearances A Appliance Dimensions NOTE Flue Collar size is 6 inch 152mm dia...

Страница 8: ... inch 152mm S635 flue liner required as per ULC S628 In USA a minimum 5 ft length 1 82m 6 inch 152mm diameter flue liner is required as per UL 1482 SIDE TRIM SIDE WALL TOP TRIM 27 1 4 692mm 32 1 4 819mm HEARTH EXTENSION USA 16 3 4 CANADA 24 3 4 629mm 40 11 16 1033mm FIREPLACE FRONT SURFACE USA 23 1 2 CANADA 25 1 2 648mm HEARTH EXTENSION 43 11 16 1110mm 12in max MANTEL No thermal protection require...

Страница 9: ...hrough the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind turbulence and down drafts Consider the appliance location in order to avoid floor and ceiling attic joists and rafters Locate termination cap away from trees adjacent structures unev...

Страница 10: ...cm Minimum 3 ft 91cm Minimum Wall or Parapet Flat Roof E 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimney connector as the flue collar on the unit Changing the diameter of the chimney can affect draft and cause poor performance It is not recommended to use offsets and elbows at altitudes above 4000 f...

Страница 11: ...or cleaning and re installation When possible install an airtight clean out door to the rear of the smoke shelf A Venting Systems Chimney Connector It is also known as flue pipe or stove pipe It must be 6 inches 152mm minimum diameter stainless steel connector pipe Chimney The chimney can be new or existing masonry or prefabricated and must meet the following minimum requirements as specified belo...

Страница 12: ...Accordance with Insert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Offset in Chimney Combustible Floor Masonry Chimney Cont d This insert conforms with the UL 1482 and ULC S628 Canada in all respects and is approved to UL ULC safety standards for installation and use within a fireplace with a masonry chimney in accordance with NFPA 211 an...

Страница 13: ...flue collar and the chimney top The air flow of the factory built zero clearance fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existing air cooled chimney system No dilution air is allowed to enter the chimney 1 Secure the fireplace damper in the open position If this cannot be accomplished it will be necessary to remove the damper ...

Страница 14: ...the fireplace opening the portion of the insert extending onto the hearth must be supported Manufacturer designed adjustable support kit can be ordered from your dealer Final approval of this installation type is contingent upon the authority having jurisdiction Fire Risk When lining air cooled factory built chimneys Run chimney liner approved to UL 1777 Type HT requirements 2100 degrees F Re inst...

Страница 15: ...perly Chimney heights exceeding 25 feet 7 62m from base of appliance may create an over draft situation Overdraft condition may create over firing Over firing may ignite creosote and or damage appliance and chimney WARNING A permit may be required for installations final approval is contingent of the authority having local jurisdiction Consult insurance carrier local building fire officials or aut...

Страница 16: ...burn properly Smoke spillage occurs when door is opened due to air starvation WARNING Option One Installation Instructions The outside air cover comes packaged with the component pack It is necessary to remove the blower housing and block off the room air with the outside air cover 1 Remove the appliance cover plate on outer can and discard and reuse the 4 screws 2 Install optional flex adapter to...

Страница 17: ...liner do not always align properly This situation may be remedied by using the optional offset adapter See Appliance Dimen sions page for the amount of distance this accessory can telescope between the flue collar and stove pipe liner 1 Remove the cast iron flue collar from the appliance and flip it upside down Using the larger 7 drill bit supplied drill through all 8 countersunk locations Figure ...

Страница 18: ...ng Figure 18 2 2 Insert the 5 16 bolts inside the cast flue and through the chimney mounting bar Securely tighten the nuts Fas teners are provided 3 Re install the tube channel assembly baffle board ceramic blanket and baffle protection channel F Surround Trim Kit Installation 1 Lay surround face down on a protected surface to pre vent scratching 2 Using a Phillips head screw driver attach the sid...

Страница 19: ... tat are made to the snap disc Disconnect the wires that attach to the snap dis Figure 20 4 8 Using pliers pry on the tabs that retain the harness enough to remove the harness Do not disconnect the wires that go to the blower Place the harness under the tabs on the left hand side of the convection housing and bend them down enough until they hold the harness Figure 20 5 9 Using pliers remove the s...

Страница 20: ...047 910 October 14 2013 5100 I ACC Figure 20 1 Figure 20 2 Remove Control Plate Remove Strain Relief Disconnect Wires to theSnap Disc Figure 20 3 Figure 20 4 Place Harness Under Tabs Figure 20 5 Figure 20 6 ...

Страница 21: ... sheet metal shears cut trim along the marked edge The cut edge fits under lip of top trim so it allows for some variance in your straight edge 5 The double sided tape that holds front and side trims to scissors has a particularly powerful bonding adhesive Adjustments are extremely difficult once trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim ...

Страница 22: ...ts from each side of insert and use plumbers tape to secure to structure a washer may be required Re install bolts 3 Unit must be grounded with 8 solid copper grounding wire or equivalent and terminated at each end with N E C approved grounding device 4 The factory built fireplace must meet UM 84 HUD requirements for outside combustion air supply to the fireplace fire chamber and the chimney must ...

Страница 23: ...it 43 X 31 Black TRIMKIT 4331 BK Gold TRIMKIT 4331 GD Nickel TRIMKIT 4331 NL Surround 51 X 34 Order Trim Kit Seperately SP 51IACC LRG Surround Trim Kit 51 X 34 Black TRIMKIT 5134 BK Gold TRIMKIT 5134 GD Nickel TRIMKIT 5134 NL Offset Adapter OFFSET ADAPT Door Upgrade Kit Spring Handles And Hinge Pins Gold UK DRGD Nickel UK DRNL Outside Air Kit OAK ACC Adjustable Hearth Support 12 X 50 2 10 H ADJSPT...

Страница 24: ...Important operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instruc tions for safe installa tion and operation DO NOT DISCARD Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com CONTACT INFORMATION This produc...

Отзывы: