7037-172
September 26, 2016
4300 Wood Appliance Series ACC
C. Clearances to Combustibles
NOTE: Clearances may only be reduced by means approved by the regulatory authority having jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
WARNING
BACKWALL / SIDEWALL
A
B
D
C
F
E
E
F
CORNER INSTALLATION
C
ALCOVE TOP VIEW
G
A
ALCOVE SIDE VIEW
G
H
STOVE TO
CEILING
CLEARANCE
*
* If H = N/A, follow Pipe Manufacturer’s
clearances
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches (Millimeters)
Note: A, C, and F Dimensions are to the center of the flue collar
4300 WOOD APPLIANCE
INSTALLATION: FULL VERTICAL OR HORIZONTAL WITH VERTICAL RISE
A
B
C
D
E
F
G
H*
SINGLE WALL PIPE
MILLENNIUM
18-1/2 (470)
11-3/4 (298)
27-1/2 (699)
14-1/2 (368)
10 (254)
20-1/2 (521)
53-1/2 (1359)
12 (305)
STEP TOP
18-1/2 (470)
11-3/4 (298)
27-1/2 (699)
14-1/2 (368)
2 (51)
15 (381)
49-1/2 (1283)
12 (305)
DOUBLE WALL PIPE
MILLENNIUM
12 (305)
5-1/4 (133)
27-1/2 (699)
14-1/2 (368)
10 (254)
20-1/2 (521)
53-1/2 (1359)
12 (305)
STEP TOP
10-1/2 (267)
3-3/4 (95)
25 (635)
11-3/4 (298)
2 (51)
15 (381)
49-1/2 (1283)
5 (127)
INSTALLATION: 90 DEGREE ELBOW OFF TOP OF STOVE THROUGH BACKWALL
DOUBLE WALL PIPE
MILLENNIUM
11-1/2 (292)
6 (152)
27-1/2 (699)
15 (381)
10 (254)
20-1/2 (521)
53-1/2 (1359)
N/A
STEP TOP
10-1/2 (267)
4 (102)
22 (559)
9 (229)
2 (51)
15 (381)
49-1/2 (1283)
N/A
INSTALLATION: ALCOVE
DOUBLE WALL PIPE
MILLENNIUM
16 (406)
10 (254)
27 (686)
14-1/2 (368)
N/A
N/A
53-1/2 (1359)
12 (305)
STEP TOP
10-1/2 (267)
3-3/4 (95)
25 (635)
11-3/4 (298)
N/A
N/A
49-1/2 (1283)
5 (127)
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A chimney or masonry
chimney. Maximum depth of Alcove shall be no more than 48 inches (1219mm) and the referenced alcove clearances. Canada must comply with
CAN/ULC-S269 M87
for the 650° factory built chimney.
* FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED
NOTE: Service Space
In order to replace the tube channel assembly a clearance
of 19 inches (483mm) is required on the right side of stove in
order to remove the tubes with the stove in place.
If space is not available, the stove will have to be discon-
nected from the chimney to proceed with the tube replace-
ment.