Hardware Installation
2. Preparation before Installation
78
www.qtech.ru
2.2
Installation Site Requirements
QSW-7600 must be used in the room. To ensure normal operation and a prolonged useful life
of the equipment, the installation site must meet the following requirements.
2.2.1
Load Bearing Requirements
Evaluate the load bearing requirements for the ground according to the weight of the switch
and its components (such as the cabinet, chassis, single board and power supply). Make sure
the installation site meet the requirements.
2.2.2
Space Requirements
❖
It is recommended that the width of the machine room corridor be greater than 0.8m to
ensure enough space for moving of chassis and plugging and removing of modules.
❖
Please do not install the switch against the wall. Instead, please leave some space around
the switch for heat dissipation and switch maintenance.
2.2.3
Ventilation Requirements
See
QSW-7608
and
QSW-7605
in
Product Overview
for their heat dissipation and ventilation
respectively. Sufficient space (10 cm at least) must be reserved at the air intakes and exhaust
vents for ventilation. After connecting various cables, you should bundle the cables or place
them in the cable management bracket to avoid blocking air intakes.
Remove all foam packaging materials and protective plastics before you power on QSW-
7608
/QSW-7605
.
2.2.4
Temperature Requirements
To ensure the normal operation and a prolonged useful life of the QSW-7600, you must
maintain an appropriate temperature in the equipment room. Too high or low temperature for
a long period of time may damage the equipment.
❖
In an environment with high temperature, the equipment is subjected to even greater
harm, as its performance may degrade significantly and its useful life may be shortened in
the case of long-term exposure that expedites the aging process.
Temperature Requirements of the QSW-7600
Operating Temperature
Storage Temperature
0ºC
to
50ºC
-40
ºC
to 70
ºC
The ambient temperature is measured at the point that is 1.5m above the floor and 0.4m
before the equipment when there is no protective plate in front or back of the equipment
rack.