First, connect the cable(s) between the system and APC smart-UPS via RS-232. Then set
up the following values for what the system will do the actions when power fails.
Figure 4.5.2.2
(Figure 4.5.2.2: With Smart-UPS.)
•
UPS column description:
UPS Type
Select UPS Type. Choose Smart-UPS for APC, None for other
vendors or no UPS.
Shutdown
battery level
(%)
When below the setting level, the system will shutdown. Setting
level to
“0”
will disable UPS.
Shutdown
delay (s)
If power failure occurs and system power can not recover after
the time setting, the system will shutdown. Setting delay to
“0”
will disable the function.
Shutdown
UPS
Select ON, when power is gone, UPS will shutdown by itself after
the system shutdown successfully. After power comes back, UPS
will start working and notify system to boot up. OFF will not.
Status
The status of UPS:
“Detecting…”
“Running”
“Unable to detect UPS”