Clearance Chart:

For safe and efficient operation, maintain at least the following
minimum clearances at all times:

Bottom of Heater to Finished Floor:

• Front Inlet Models: (max 600 watts per foot) 

-  May be installed on floor.  However, for best performance,
install bottom of heater approximately 3 inches (76 mm) off floor.

• Bottom Inlet Models: 

-  100-250 watts per foot – 1-3/4 inch (44 mm)

-  375-750 watts per foot – 3 inches (76 mm) 

Top of Heater to Ceiling (all models):

-  Minimum 36 inches (914 mm) 

Top of Heater to Bottom of Drapes Above Heater:

-  Minimum 12 inches (305 mm)

IMPORTANT NOTE: Certain fabrics and vinyl materials (such
as vinyl blinds) may become damaged by the heated air from
the heater and should not be installed above the heater.

Front of Heater to Full Length Drapes in Front of Heater:

-  Minimum between bottom of drapes and floor – 2-1/2 inches
(64 mm)

-  Minimum between top of drapes and ceiling – 1/2 inch (13
mm)

-  Minimum between front of heater and nearest fold of drape –
2 inches (51 mm)

Top of Heater to Bottom of Window Sill:

-  Minimum 12 inches (305 mm)

2

No. 12 AWG
No. 10 AWG

No. 8 AWG

9
8
4

11.5 Amps
17.4 Amps
24.0 Amps

9.3 Amps

14.0 Amps
21.0 Amps

8.1 Amps

12.1 Amps

-

Copper wire

size 90º C

Max. No.

wire installed

in wireway

Up to 3 

conductors

4 to 6 

conductors

7 to 9 

conductors

Maximum Allowable Current

Table B. Sizing Field Installed Wiring

Catalog

Length

Watts

Total

Amperage

Number

"L"

per ft.

Watts

120V

208V

240V

277V

347V

600V

02100

100

200

1.7

1.0

0.8

--

--

--

02125

28"

125

250

2.1

1.2

1.0

0.9

--

--

02150

(711mm)

150

300

2.5

1.4

1.3

1.1

--

--

02188

188

376

3.1

1.8

1.6

1.4

--

--

02250

250

500

4.2

2.4

2.1

1.8

1.4

--

03100

100

300

2.5

1.4

1.3

1.1

--

--

03125

3'

125

375

3.1

1.8

1.6

1.4

1.1

--

03150

(914mm)

150

450

3.8

2.2

1.9

1.6

1.3

--

03188

188

564

4.7

2.7

2.4

2.0

1.6

--

03250

250

750

6.3

3.6

3.1

2.7

2.2

--

04100

100

400

3.3

1.9

1.7

1.4

1.2

--

04125

4'

125

500

4.2

2.4

2.1

1.8

1.4

--

04150

(1219mm)

150

600

5.0

2.9

2.5

2.2

1.7

--

04188

188

752

6.3

3.6

3.1

2.7

2.2

1.3

04250

250

1000

8.3

4.8

4.2

3.6

2.9

1.7

05100

100

500

4.2

2.4

2.1

1.8

1.4

0.8

05125

5'

125

625

5.2

3.0

2.6

2.3

1.8

1.0

05150

(1524mm)

150

750

6.3

3.6

3.1

2.7

2.2

1.3

05188

188

940

7.8

4.5

3.9

3.4

2.7

1.6

05250

250

1250

10.4

6.0

5.2

4.5

3.6

2.1

06100

100

600

5.0

2.9

2.5

2.2

1.7

1.0

06125

6'

125

750

6.3

3.6

3.1

2.7

2.2

1.3

06150

(1829mm)

150

900

7.5

4.3

3.8

3.2

2.6

1.5

06188

188

1128

9.4

5.4

4.7

4.1

3.3

1.9

06250

250

1500

12.5

7.2

6.3

5.4

4.3

2.5

07100

100

700

--

3.4

2.9

2.5

2.0

1.2

07125

7'

125

875

--

4.2

3.6

3.2

2.5

1.5

07150

(2134mm)

150

1050

--

5.0

4.4

3.8

3.0

1.8

07188

188

1316

--

6.3

5.5

4.8

3.8

2.2

07250

250

1750

--

8.4

7.3

6.3

5.0

2.9

08100

100

800

--

3.8

3.3

2.9

2.3

1.3

08125

8'

125

1000

--

4.8

4.2

3.6

2.9

1.7

08150

(2438mm)

150

1200

--

5.8

5.0

4.3

3.5

2.0

08188

188

1504

--

7.2

6.3

5.4

4.3

2.5

08250

250

2000

--

9.6

8.3

7.2

5.8

3.3

09100

100

900

--

4.3

3.8

3.2

2.6

1.5

09125

9'

125

1125

--

5.4

4.7

4.1

3.2

1.9

09150

(2743mm)

150

1350

--

6.5

5.6

4.9

3.9

2.3

09188

188

1692

--

8.1

7.1

6.1

4.9

2.8

09250

250

2250

--

10.8

9.4

8.1

6.5

3.8

10100

100

1000

--

4.8

4.2

3.6

2.9

1.7

10125

10'

125

1250

--

6.0

5.2

4.5

3.6

2.1

10150

(3048mm)

150

1500

--

7.2

6.3

5.4

4.3

2.5

10188

188

1880

--

9.0

7.8

6.8

5.4

3.1

10250

250

2500

--

12.0

10.4

9.0

7.2

4.2

Table A - DBA & SHA 

(one element)

Amperage

Catalog

Length

Watts

Total

208V

240V

277V

347V

600V

Number

"L"

per ft.

Watts

1 Ph 3 Ph

1 Ph

3 Ph

1 Ph

1 Ph

1 Ph

3 Ph

02375

375

750

3.6

-

3.1

-

2.7

-

-

-

02500

28"

500

1000

4.8

-

4.2

-

3.6

2.9

-

-

02600

(711mm)

600

1200

5.8

3.3

5.0

2.9

4.3

-

-

-

02750*

750

1500

7.2

4.2

6.3

3.6

5.4

4.3

-

-

03375

375

1125

5.4

-

4.7

-

4.1

-

-

-

03500

3'

500

1500

7.2

-

6.3

-

5.4

4.3

-

-

03600

(914mm)

600

1800

8.7

5.0

7.5

4.3

6.5

-

-

-

03750*

750

2250

10.8

6.3

9.4

5.4

8.1

6.5

-

-

04375

375

1500

7.2

-

6.3

-

5.4

4.3

-

-

04500

4'

500

2000

9.6

-

8.3

-

7.2

5.8

3.3

-

04600

(1219mm)

600

2400

11.5

6.7

10.0

5.8

8.7

6.9

-

-            

04750*

750

3000

14.4

8.3

12.5

7.2

10.8

8.6

5.0

2.9

05375

375

1875

9.0

-

7.8

-

6.8

5.4

3.1

-

05500

5'

500

2500

12.0

-

10.4

-

9.0

7.2

4.2

-

05600

(1524mm)

600

3000

14.4

8.3

12.5

7.2

10.8

8.6

5.0

2.9

05750*

750

3750

18.0

10.4

15.6

9.0

13.5

10.8

6.3

3.6

06375

375

2250

10.8

-

9.4

-

8.1

6.5

3.8

-

06500

6'

500

3000

14.4

-

12.5

-

10.8

8.6

5.0

-

06600

(1829mm)

600

3600

17.3

10.0

15.0

8.7

13.0

10.4

6.0

3.5

06750*

750

4500

21.6

12.5

18.8

10.8

16.2

13.0

7.5

4.3

07375

375

2625

12.6

-

10.9

-

9.5

7.6

4.4

-

07500

7'

500

3500

16.8

-

14.6

-

12.6

10.1

5.8

-

07600

(2134mm)

600

4200

20.2

11.7

17.5

10.1

15.2

12.1

7.0

4.0

07750*

750

5250

25.2

14.6

21.9

12.6

19.0

15.1

8.8

5.1

08375

375

3000

14.4

-

12.5

-

10.8

8.6

5.0

-

08500

8'

500

4000

19.2

-

16.7

-

14.4

11.5

6.7

-

08600

(2438mm)

600

4800

23.1

13.3

20.0

11.6

17.3

13.8

8.0

4.6

08750*

750

6000

28.8

16.7

25.0

14.5

21.7

17.3

10.0

5.8

09375

375

3375

16.2

-

14.1

-

12.2

9.7

5.6

-

09500

9'

500

4500

21.6

-

18.8

-

16.2

13.0

7.5

-

09600

(2743mm)

600

5400

26.0

15.0

22.5

13.0

19.5

15.6

9.0

5.2

09750*

750

6750

32.5

18.8

28.1

16.3

24.4

19.5

11.3

6.5

10375

375

3750

18.0

-

15.6

-

13.5

10.8

6.3

-

10500

10'

500

5000

24.0

-

20.8

-

18.1

14.4

8.3

-

10600

(3048mm)

600

6000

28.8

16.7

25.0

14.5

21.7

17.3

10.0

5.8

10750*

750

7500

36.1

20.8

31.3

18.1

27.1

21.6

12.5

7.2

SHA 

(two and three element) 

*Bottom inlet only

Table C. Maximum Length of Heater Run

Watts/Ft 

Max. allowable length of heater run in feet (meters) 

of 

120V

208V

240V

277V

347V

600V

Heaters

1 Ph

1 Ph

3 Ph

1 Ph

3 Ph

1 Ph

1 Ph

1 Ph

3 Ph

100

54 (16)

93 (28)

-

108 (33)

-

124 (38)

156 (47)

270 (82)

467 (142)

125

43 (13)

74 (23)

-

86 (26)

-

99 (30)

125 (38)

216 (66)

373 (113)

150

36 (11)

62 (19)

-

72 (22)

-

83 (25)

104 (32)

180 (55)

311 (95)

188

28 (9)

49 (15)

-

57 (17)

-

66 (20)

83 (25)

146 (45)

248 (76)

250

21 (6)

37 (11)

-

43 (13)

-

49 (15)

62 (19)

108 (33)

186 (57)

375

-

34 (7)

-

28 (9)

-

33 (10)

42 (13)

72 (22)

125 (38)

500

-

18 (5)

-

21 (6)

-

24 (7)

31 (9)

54 (16)

93 (28)

600

-

15 (5)

27 (8)

18 (5)

31 (9)

20 (6)

26 (8)

45 (14)

78 (24)

750

-

12 (4)

21 (6)

14 (4)

24 (7)

16 (5)

21 (6)

36 (11)

62 (19)

Содержание DBA

Страница 1: ...exhaust in any manner 5 Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock or fire or damage the heater 6 Serious injury or death co...

Страница 2: ...8188 188 1504 7 2 6 3 5 4 4 3 2 5 08250 250 2000 9 6 8 3 7 2 5 8 3 3 09100 100 900 4 3 3 8 3 2 2 6 1 5 09125 9 125 1125 5 4 4 7 4 1 3 2 1 9 09150 2743mm 150 1350 6 5 5 6 4 9 3 9 2 3 09188 188 1692 8 1...

Страница 3: ...SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING 1 Serious injury or death could result from electric shock Make sure electrical power supply circuit coming to heater are disconnected at main disconn...

Страница 4: ...E If a heater has a disconnect switch and or thermostat and is to have a filler section at the left end the filler must not cover the access to those controls 4 If the run of the heaters includes an i...

Страница 5: ...sure it has adequate clearances and the free airflow around heater is not restricted If heater continues to cycle on this safety control discontinue using until it can be inspected and or repaired by...

Страница 6: ...BILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CO...

Страница 7: ...rico o incendio o de da os al calefactor 6 Un choque el ctrico podr a producir lesiones graves o la muerte Aseg rese de que el circuito de alimentaci n el ctrica del calefactor est desconectado en el...

Страница 8: ...4125 4 125 500 4 2 2 4 2 1 1 8 1 4 04150 1219 mm 150 600 5 0 2 9 2 5 2 2 1 7 04188 188 752 6 3 3 6 3 1 2 7 2 2 1 3 04250 250 1000 8 3 4 8 4 2 3 6 2 9 1 7 05100 100 500 4 2 2 4 2 1 1 8 1 4 0 8 05125 5...

Страница 9: ...o podr a producir lesiones graves o la muerte Aseg rese de que el circuito de alimentaci n el ctrica del calefac tor est desconectado en el tablero de servicio o desconectador principal antes de insta...

Страница 10: ...ecci n de relleno en el extremo izquierdo sta no debe cubrir el acceso a esos controles 4 Si el tramo de los calefactores incluye una esquina interior o una esquina exterior monte la esquina contra la...

Страница 11: ...de aire alrededor del calefactor no se encuentre restringida Si el calefactor contin a haciendo ciclos con este control de seguridad interrumpa su uso hasta que lo pueda inspeccionar y o reparar un el...

Страница 12: ...ODUCTS NO SE HAR RESPONSABLE POR DA OS CONSIGUIENTES QUE SE PRODUZCAN CON RESPECTO AL PRODUCTO EN BASE YA SEA A NEGLIGENCIA AGRAVIO RESPONSABILIDAD ESTRICTA O CONTRATO Algunos estados o jurisdicciones...

Страница 13: ...tincelles lectriques Ne l utilisez pas dans des zones o de l essence ou des liq uides inflammables sont utilis s 3 Ce radiateur est chaud quand il est en fonctionnement Pour viter des br lures ne lai...

Страница 14: ...Total en 208 V 240 V 277 V 347 V 600 V catalogue L par pied watts 1 Ph 3 Ph 1 Ph 3 Ph 1 Ph 1 Ph 1 Ph 3 Ph 02375 375 750 3 6 3 1 2 7 02500 28 500 1000 4 8 4 2 3 6 2 9 02600 711 mm 600 1200 5 8 3 3 5 0...

Страница 15: ...ESSURES AUX PERSONNES OBSERVEZ LES CONSIGNES SUIVANTES 1 Une blessure s rieuse voire mortelle peut r sulter d une commo tion lectrique Assurez vous que le circuit du secteur d alimenta tion lectrique...

Страница 16: ...mit de gauche cette section ne doit pas couvrir l acc s ces commandes 4 Si l ensemble des radiateurs comprend un angle rentrant ou saillant montez d abord cet angle sur la cloison voyez les instructi...

Страница 17: ...s par le dispositif de s curit cessez de l utiliser avant qu il ait t inspect et ou r par par un lectricien qualifi INSTRUCTIONS D ENTRETIEN Votre radiateur vous fournira des ann es de bon service et...

Страница 18: ...s frais de main d uvre et les frais de port encourus pour retourner le produit au centre de r paration de la soci t Marley Engineered Products Sous r serve des restrictions figurant dans cette garanti...

Отзывы: